Section 110.3 Mandatory Requirements for Service Water-Heating Systems and Equipment
Go To Full Code Chapter
- Certification by manufacturers. Any service waterheating system or equipment may be installed only if the manufacturer has certified that the system or equipment complies with all of the requirements of this subsection for that system or equipment.
- Temperature controls for service water-heating systems. Service water-heating systems shall be equipped with automatic temperature controls capable of adjustment from the lowest to the highest acceptable temperature settings for the intended use as listed in Table 3, Chapter 50 of the ASHRAE Handbook, HVAC Applications Volume or Table 613.1 of the California Plumbing Code for healthcare facilities.Exception to Section 110.3(a)1: Residential occupancies.
- Temperature controls for service water-heating systems. Service water-heating systems shall be equipped with automatic temperature controls capable of adjustment from the lowest to the highest acceptable temperature settings for the intended use as listed in Table 3, Chapter 50 of the ASHRAE Handbook, HVAC Applications Volume or Table 613.1 of the California Plumbing Code for healthcare facilities.
- Efficiency. Equipment shall meet the applicable requirements of the Appliance Efficiency Regulations as required by Section 110.1, subject to the following:
- If more than one standard is listed in the Appliance Efficiency Regulations, the equipment shall meet all the standards listed; and
- If more than one test method is listed in the Appliance Efficiency Regulations, the equipment shall comply with the applicable standard when tested with each test method; and
- Where equipment can serve more than one function, such as both heating and cooling, or both space heating and water heating, it shall comply with all the requirements applicable to each function; and
- Where a requirement is for equipment rated at its "maximum rated capacity" or "minimum rated capacity," the capacity shall be as provided for and allowed by the controls, during steady-state operation.
- Installation. Any service water-heating system or equipment may be installed only if the system or equipment complies with all of the applicable requirements of this subsection for the system or equipment.
- Outlet temperature controls. On systems that have a total capacity greater than 167,000 Btu/hr, outlets that require higher than service water temperatures as listed in the ASHRAE Handbook, Applications Volume, shall have separate remote heaters, heat exchangers or boosters to supply the outlet with the higher temperature.Exception to Section 110.3(c)1: Systems covered by California Plumbing Code Section 613.0 shall instead follow the requirements of that section.
- Controls for hot water distribution systems. Service hot water systems with circulating pumps or with electrical heat trace systems shall be capable of automatically turning off the system.Exception to Section 110.3(c)2: Systems serving healthcare facilities.
- Insulation. Unfired service water heater storage tanks and backup tanks for solar water-heating systems shall have:
- External insulation with an installed R-value of at least R-3.5; or
- Internal and external insulation with a combined R-value of at least R-16; or
- The heat loss of the tank surface based on an 80°F water-air temperature difference shall be less than 6.5 Btu per hour per square foot.
- Water heating recirculation loops serving multiple dwelling units, high-rise residential, hotel/motel, and nonresidential occupancies. A water heating recirculation loop is a type of hot water distribution system that reduces the time needed to deliver hot water to fixtures that are distant from the water heater, boiler or other water heating equipment. The recirculation loop is comprised of a supply portion, connected to branches that serve multiple dwelling units, guest rooms, or fixtures and a return portion that completes the loop back to the water heating equipment. A water heating recirculation loop shall meet the following requirements:
- Air release valve or vertical pump installation. An automatic air release valve shall be installed on the recirculation loop piping on the inlet side of the recirculation pump and no more than 4 feet from the pump. This valve shall be mounted on top of a vertical riser at least 12 inches in length and shall be accessible for replacement and repair. Alternatively, the pump shall be installed on a vertical section of the return line.
- Recirculation loop backflow prevention. A check valve or similar device shall be located between the recirculation pump and the water heating equipment to prevent water from flowing backwards though the recirculation loop.
- Equipment for pump priming. A hose bibb shall be installed between the pump and the water heating equipment. An isolation valve shall be installed between the hose bibb and the water heating equipment. This hose bibb is used for bleeding air out of the pump after pump replacement.
- Pump isolation valves. Isolation valves shall be installed on both sides of the pump. These valves may be part of the flange that attaches the pump to the pipe. One of the isolation valves may be the same isolation valve as in Item C.
- Cold water supply and recirculation loop connection to hot water storage tank. Storage water heaters and boilers shall be plumbed in accordance with the manufacturer's specifications The cold water piping and the recirculation loop piping shall not be connected to the hot water storage tank drain port.
- Cold water supply backflow prevention. A check valve shall be installed on the cold water supply line between the hot water system and the next closest tee on the cold water supply line. The system shall comply with the expansion tank requirements as described in the California Plumbing Code Section 608.3.
- Service water heaters in state buildings. Any newly constructed building constructed by the State shall derive its service water heating from a system that provides at least 60 percent of the energy needed for service water heating from site solar energy or recovered energy, per the statutory requirement of California Public Resources Code Section 25498.Exception to Section 110.3(c)5: Buildings for which the state architect determines that service water heating from site solar energy or recovered energy is economically or physically infeasible.
- Isolation valves. Instantaneous water heaters with an input rating greater than 6.8 kBTU/hr (2 kW) shall have isolation valves on both the cold water supply and the hot water pipe leaving the water heater, and hose bibbs or other fittings on each valve for flushing the water heater when the valves are closed.
- Outlet temperature controls. On systems that have a total capacity greater than 167,000 Btu/hr, outlets that require higher than service water temperatures as listed in the ASHRAE Handbook, Applications Volume, shall have separate remote heaters, heat exchangers or boosters to supply the outlet with the higher temperature.
Related Code Sections
Section 110.3 All Occupancies—Mandatory Requirements for the Manufacture, Construction and Installation of Systems, Equipment and Building Components, Mandatory Requirements for Service Water-Heating Systems and Equipment
(a) Certification by manufacturers. Any service water-heating system or equipment may be installed only if the manufacturer has certified ...
Section 110.3 All Occupancies — Mandatory Requirements for the Manufacture, Construction and Installation of Systems, Equipment and Building Components, Mandatory Requirements for Service Water-Heating Systems and Equipment
or equipment complies with all of the requirements of this subsection for that system or equipment. Temperature controls for service water-heating ...
Section 110.3 All Occupancies—Mandatory Requirements for the Manufacture, Construction and Installation of Systems, Equipment and Building Components, Mandatory Requirements for Service Water-Heating Systems and Equipment
or equipment complies with all of the requirements of this subsection for that system or equipment. Temperature controls for service water-heating ...
501.2 Water Heaters, California Energy Code Water Heating System Requirements [CEC]
See California Energy Code Section 110.3 for additional mandatory requirements for all service water heating systems, and 150.0(n) for additional ...
Section 160.4 Multifamily Buildings—Mandatory Requirements, Mandatory Requirements for Water-Heating Systems
of at least 200,000 Btu/hr. Water-heating recirculation loops serving multiple dwelling units shall meet the requirements of Section 110.3(c)4. Solar ...