A1301.9.5 Makeup Water
JUMP TO FULL CODE CHAPTER
Where an uninterrupted supply is required for the intended application, potable or reclaimed water shall be provided as a source of makeup water for the storage tank. The makeup water supply shall be protected against back-flow in accordance with Section 608. A full-open valve located on the makeup water supply line to the storage tank shall be provided. Inlets to the storage tank shall be controlled by fill valves or other automatic supply valves installed to prevent the tank from overflowing and to prevent the water level from dropping below a predetermined point. Where makeup water is provided, the water level shall not be permitted to drop below the source water inlet or the intake of any attached pump.
Related Code Sections
1207.2 Hydronic Piping, Makeup Water
The transfer fluid shall be compatible with the makeup water supplied to the system ...
1210.9 Hydronic Piping, Makeup Water
The transfer fluid shall be compatible with the makeup water supplied to the system ...
2015 Michigan Mechanical Code > 12 Hydronic Piping > 1210 Plastic Pipe Ground-Source Heat Pump Loop Systems > 1210.9 Makeup Water
A1301.9.5 Nonpotable Water Systems, Makeup Water
Where an uninterrupted supply is required for the intended application, potable or reclaimed water shall be provided as a source of makeup water ...
2015 Michigan Plumbing Code > A Nonpotable Water Systems > A1301 General > A1301.9 Nonpotable Water Storage Tanks > A1301.9.5 Makeup Water
M2105.27 Hydronic Piping, Makeup Water
The transfer fluid shall be compatible
with the makeup water supplied to the system ...
2015 Michigan Residential Code > 21 Hydronic Piping > M2105 Ground-Source Heat-Pump System Loop Piping > M2105.27 Makeup Water
P2910.9.5 Water Supply and Distribution, Makeup Water
of
makeup water for the storage tank. The makeup water supply
shall be protected against backflow by means of an air
gap not less than 4 inches (102 mm ...