506.3.1.2 Makeup Air Ducts
JUMP TO FULL CODE CHAPTER
Makeup air ducts connecting to or within 18 inches (457 mm) of a Type I hood shall be constructed and installed in accordance with Sections 603.1, 603.3, 603.4, 603.9, 603.10 and 603.12. Duct insulation installed within 18 inches (457 mm) of a Type I hood shall be noncombustible or shall be listed for the application.
Related Code Sections
506.3.1.2 Exhaust Systems, Makeup Air Ducts
Makeup air ducts connecting to or within 18 inches (457 mm) of a Type I hood shall be constructed and installed in accordance with Sections 603.1 ...
2017 FBC - Mechanical, 6th edition > 5 Exhaust Systems > 506 Commercial Kitchen Hood Ventilation System Ducts and Exhaust Equipment > 506.3 Ducts Serving Type I Hoods > 506.3.1 Duct Materials > 506.3.1.2 Makeup Air Ducts
506.3.1.2 Exhaust Systems, Makeup Air Ducts
Makeup air ducts connecting to or within 18 inches (457 mm) of a Type I hood shall be constructed and installed in accordance with Sections 603.1 ...
2014 FBC - Mechanical, 5th edition > 5 Exhaust Systems > 506 Commercial Kitchen Hood Ventilation System Ducts and Exhaust Equipment > 506.3 Ducts Serving Type I Hoods > 506.3.1 Duct Materials > 506.3.1.2 Makeup Air Ducts
506.3.1.2 Exhaust Systems, Makeup Air Ducts
Makeup air ducts connecting to or within 18 inches (457 mm) of a Type I hood shall be constructed and installed in accordance with Sections 603.1 ...
2020 FBC - Mechanical, 7th edition > 5 Exhaust Systems > 506 Commercial Kitchen Hood Ventilation System Ducts and Exhaust Equipment > 506.3 Ducts Serving Type I Hoods > 506.3.1 Duct Materials > 506.3.1.2 Makeup Air Ducts
1105.6.2 Refrigeration, Makeup Air
Provisions shall be made for makeup air to replace that being exhausted. Openings for makeup air shall be located to avoid intake of exhaust air ...
2014 FBC - Mechanical, 5th edition > 11 Refrigeration > 1105 Machinery Room, General Requirements > 1105.6 Ventilation > 1105.6.2 Makeup Air
1105.6.2 Refrigeration, Makeup Air
Provisions shall be made for makeup air to replace that being exhausted. Openings for makeup air shall be located to avoid intake of exhaust air ...
2017 FBC - Mechanical, 6th edition > 11 Refrigeration > 1105 Machinery Room, General Requirements > 1105.6 Ventilation > 1105.6.2 Makeup Air