// CODE SNIPPET
Section 1031 Maintenance of the Means of Egress
JUMP TO FULL CODE CHAPTER
The means of egress for buildings or portions thereof shall be maintained in accordance with this section.
Required exit accesses, exits and exit discharges shall be continuously maintained free from obstructions or impediments to full instant use in the case of fire or other emergency where the building area served by the means of egress is occupied. An exit or exit passageway shall not be used for any purpose that interferes with a means of egress.
Security devices affecting means of egress shall be subject to approval of the fire code official. Security devices and locking arrangements in the means of egress that restrict, control, or delay egress shall be installed and maintained as required by this chapter.
A means of egress shall be free from obstructions that would prevent its use, including the accumulation of snow and ice.
In Group I-2, the required clear width for aisles, corridors and ramps that are part of the required means of egress shall comply with Section 1020.2. The facility shall have a plan to maintain the required clear width during emergency situations.
Exception: In areas required for bed movement, equipment shall be permitted in the required width where all the following provisions are met:
Exception: In areas required for bed movement, equipment shall be permitted in the required width where all the following provisions are met:
- 1. The equipment is low hazard and wheeled.
- 2. The equipment does not reduce the effective clear width for the means of egress to less than 5 feet (1525 mm).
- 3. The equipment is limited to:
- 3.1 Equipment and carts in use.
- 3.2 Medical emergency equipment.
- 3.3 Infection control carts.
- 3.4 Patient lift and transportation equipment.
- 4. Medical emergency equipment and patient lift and transportation equipment, when not in use, is required to be located on one side of the corridor.
- 5. The equipment is limited in number to a maximum of one per patient sleeping room or patient care room within each smoke compartment.
Exit signs shall be installed and maintained in accordance with Section 1013. Decorations, furnishings, equipment or adjacent signage that impairs the visibility of exit signs, creates confusion or prevents identification of the exit shall not be allowed.
Where a door is adjacent to, constructed similar to and can be confused with a means of egress door, that door shall be identified with an approved sign that identifies the room name or use of the room.
Means of egress doors shall be maintained in such a manner as to be distinguishable from the adjacent construction and finishes such that the doors are easily recognizable as doors. Furnishings, decorations or other objects shall not be placed so as to obstruct exits, access thereto, egress therefrom, or visibility thereof. Hangings and draperies shall not be placed over exit doors or otherwise be located to conceal or obstruct an exit. Mirrors shall not be placed on exit doors. Mirrors shall not be placed in or adjacent to any exit in such a manner as to confuse the direction of exit.
Required emergency escape and rescue openings shall be maintained in accordance with the code in effect at the time of construction, and the following: Required emergency escape and rescue openings shall be operational from the inside of the room without the use of keys or tools. Bars, grilles, grates or similar devices are allowed to be placed over emergency escape and rescue openings provided the minimum net clear opening size complies with the code that was in effect at the time of construction and such devices shall be releasable or removable from the inside without the use of a key, tool or force greater than that which is required for normal operation of the emergency escape and rescue openings.
All two-way communication systems for areas of refuge shall be inspected and tested on a yearly basis to verify that all components are operational. Where required, the tests shall be conducted in the presence of the fire code official. Records of inspection, testing and maintenance shall be maintained.
The occupant load of buildings or portions of buildings
shall not exceed the capacity of the means of egress from the buildings or portions thereof.
Occupant load shall be calculated as provided in Section 1004.1. Capacity of the means of
egress shall be calculated as provided in Sections 1005 and 1006.
Every room or space that is an assembly occupancy shall
have the occupant load of the room or space posted in a conspicuous place, near the main exit
or exit access doorway from the room or space. Posted signs shall be of an approved, legible,
permanent design and shall be maintained by the owner or authorized agent.
Related Code Sections
Section 1028 Means of Egress, Maintenance of the Means of Egress
The means of egress for buildings or portions thereof shall be maintained in accordance with this section ...
Section 1031 Means of Egress, Maintenance of the Means of Egress
The means of egress for buildings or portions thereof shall be maintained in accordance with this section ...
Section 1031 Means of Egress, Maintenance of the Means of Egress
The means of egress for buildings or portions thereof shall be maintained in accordance with this section ...
1505.2 Construction Safeguards, Maintenance of Means of Egress
Means of egress and required accessible means of egress shall be maintained at all times during construction, demolition, remodeling or alterations ...
2020 Existing Building Code of NYS > 15 Construction Safeguards > 1505 Means of Egress > 1505.2 Maintenance of Means of Egress
1505.2 Construction Safeguards, Maintenance of Means of Egress
Required means of egress shall be maintained at all times during construction, demolition, remodeling or alterations and additions to any ...
Existing Building Code 2015 of New York State > 15 Construction Safeguards > 1505 Means of Egress > 1505.2 Maintenance of Means of Egress