680.13 Maintenance Disconnecting Means
Go To Full Code Chapter
One or more means to simultaneously disconnect all ungrounded conductors shall be provided for all utilization equipment other than lighting. Each means shall be readily accessible and within sight from its equipment and shall be located at least 1.5 m (5 ft) horizontally from the inside walls of a pool, spa, fountain, or hot tub unless separated from the open water by a permanently installed barrier that provides a 1.5 m (5 ft) reach path or greater. This horizontal distance shall be measured from the water's edge along the shortest path required to reach the disconnect.
Related Code Sections
680.13 Special Equipment, Maintenance Disconnecting Means
One or more means to simultaneously disconnect all ungrounded conductors shall be provided for all utilization equipment other than lighting. Each ...
680.13 Special Equipment, Maintenance Disconnecting Means
One or more means to simultaneously disconnect all ungrounded conductors shall be provided for all utilization equipment other than lighting. Each ...
(C) Special Conditions, Storage System Maintenance Disconnecting Means
ungrounded and grounded circuit conductor(s) in the electrical storage system for maintenance. This disconnecting means shall not disconnect the grounded ...
393.21 Wiring Methods and Materials, Disconnecting Means
A disconnecting means for the Class 2 supply to the power grid system shall be located so as to be accessible and within sight of the Class 2 power ...
393.21 Wiring Methods and Materials, Disconnecting Means
A disconnecting means for the Class 2 supply to the power grid system shall be located so as to be accessible and within sight of the Class 2 power ...