Code calculators: Code Calculators automatically generates a detailed list of requirements.
REFERENCE
Amendment Styling
Industry-leading search
Suggested code sections
Code diagrams
RESEARCH
Code calculators
Filter by topic
Code compare
Code sheet exports
COLLABORATION
Team projects
Bookmarks
Comments
START 2 WEEK FREE TRIAL
Have an account? Sign in
// CODE SNIPPET

1310.2.1 Mains and Branches

California Plumbing Code 2019 > 13 Health Care Facilities and Medical Gas and Medical Vacuum Systems > 1310.0 Installation of Piping > 1310.2 Required Pipe Sizing > 1310.2.1 Mains and Branches
JUMP TO FULL CODE CHAPTER
Mains and branches in medical gas piping systems shall be not less than DN15 (NPS 1/2) (5/8 inch O.D.) size. Mains and branches in medical-surgical vacuum systems shall be not less than DN20 (NPS 3/4) (7/8 inch O.D.) size. [NFPA 99:5.1.10.11.1.2, 5.1.10.11.1.3]

TABLE 1310.2.1(1)
SYSTEM SIZING - FLOW REQUIREMENTS FOR STATION OUTLETS AND INLETS1
NUMBER OF OUTLETS AND INLETS TERMINAL UNITS PER FACILITY DIVERSITY PERCENTAGE OF AVERAGE FLOW PER OUTLETS AND INLETS TERMINAL UNITS MINIMUM PERMISSIBLE SYSTEM FLOW OF ALL PRESSURIZED MEDICAL GAS SYSTEMS2 (standard cubic feet per minute)
1-10 100% Actual Demand
11-25 75% 7.0
26-50 50% 13.1
51- 100 50% 17.5

Notes:
  • 1 Flow rates of station outlets and inlets in accordance with Table 1305.2.
  • 2 The minimum system flow is the average outlets and inlets flow times the number of station outlets and inlets times the diversity percentage.


TABLE 1310.2.1(2)
PRESSURE LOSS FOR MEDICAL AIR
FLOW RATE (SCFM)1 PRESSURE DROP (psi) PER 100 FEET2
1/2 INCH PIPE 3/4 INCH PIPE 1 INCH PIPE
0.35 0.004 0.001 -
0.71 0.012 0.003 -
1.06 0.023 0.005 -
1.41 0.037 0.007 -
1.77 0.055 0.011 -
2.12 0.075 0.015 -
2.47 0.097 0.019 -
2.82 0.123 0.024 -
3.18 0.151 0.029 -
3.53 0.181 0.035 -
4.24 0.249 0.048 -
4.94 0.326 0.063 -
5.65 0.413 0.080 -
6.36 0.507 0.098 -
7.06 0.611 0.118 0.030
7.77 0.723 0.139 0.035
8.47 0.843 0.162 0.041
9.18 0.969 0.187 0.047
9.89 1.108 0.212 0.053
10.59 1.252 0.240 0.060
12.36 1.647 0.315 0.079
14.12 2.090 0.398 0.100
15.89 2.580 0.490 0.123
17.66 3.116 0.591 0.148
19.42 - 0.701 0.176
21.19 - 0.818 0.205
22.95 - 0.944 0.236
24.72 - 1.078 0.268
28.25 - 1.369 0.341
31.78 - 1.690 0.421
35.31 - 2.043 0.509
38.84 - 2.425 0.603
42.37 - 2.838 0.705
45.90 - 3.280 0.814
49.43 - 3.751 0.929
52.97 - 4.249 1.052
56.50 - - 1.181
60.03 - - 1.318
63.56 - - 1.461
67.09 - - 1.611
70.62 - - 1.768
81.21 - - 2.276
88.28 - - 2.647
95.34 - - 3.044


For SI units: 1 standard cubic foot per minute = 28.32 SLPM, 1 inch = 25 mm, 1 foot = 304.8 mm, 1 pound-force per square inch = 6.8947 kPa

Notes:
  • 1 Based on the pressure of 14.7 psig (101 kPa) at 68°F (20°C).
  • 2 Based on the pressure of 55 psig (379 kPa) at 68°F (20°C).


TABLE 1310.2.1(3)
PRESSURE LOSS FOR MEDICAL AIR
FLOW RATE (SCFM)1 PRESSURE DROP (psi) PER 100 FEET2
1/2 INCH PIPE 3/4 INCH PIPE 1 INCH PIPE
5.30 0.126 0.024 -
10.59 0.430 0.082 -
15.89 0.886 0.168 -
21.19 1.485 0.281 -
26.48 2.220 0.419 -
31.78 3.089 0.581 -
37.08 4.087 0.766 -
42.37 - 0.975 -
47.67 - 1.206 -
52.97 - 1.460 0.361
58.26 - 1.736 0.429
63.56 - 2.033 0.502
68.85 - 2.352 0.580
74.15 - 2.692 0.663
79.45 - 3.054 0.752
84.74 - 3.436 0.845
90.04 - 3.840 0.943
95.34 - 4.264 1.046
100.63 - 4.709 1.154
105.93 - - 1.267
116.52 - - 1.508
127.12 - - 1.768
137.71 - - 2.046
148.30 - - 2.344
158.90 - - 2.660
169.49 - - 2.994
180.08 - - 3.347
190.67 - - 3.719
201.27 - - 4.108
211.86 - - 4.516
222.45 - - 4.942
233.05 - - -
243.64 - - -
254.23 - - -
264.83 - - -
275.42 - - -
286.01 - - -
296.60 - - -
307.20 - - -
317.79 - - -


For SI units: 1 standard cubic foot per minute = 28.32 SLPM, 1 inch = 25 mm, 1 foot = 304.8 mm, 1 pound-force per square inch = 6.8947 kPa

Notes:
  • 1 Based on the pressure of 14.7 psig (101 kPa) at 68°F (20°C).
  • 2 Based on the pressure of 55 psig (379 kPa) at 68°F (20°C).


TABLE 1310.2.1(4)
PRESSURE LOSS FOR NITROUS OXIDE AND CARBON DIOXIDE
FLOW RATE (SCFM)1 PRESSURE DROP (psi) PER 100 FEET2
1/2 INCH PIPE 3/4 INCH PIPE 1 INCH PIPE
0.35 0.004 - -
0.71 0.014 - -
1.06 0.029 - -
1.41 0.047 - -
1.77 0.070 - -
2.12 0.096 - -
2.47 0.125 - -
2.82 0.159 - -
3.18 0.195 - -
3.53 0.235 0.045 -
4.24 0.324 0.062 -
4.94 0.425 0.081 -
5.65 0.539 0.103 -
6.36 0.664 0.127 -
7.06 0.802 0.153 0.038
7.77 0.950 0.181 0.045
8.47 1.110 0.211 0.053
9.18 1.281 0.243 0.061
9.89 1.463 0.278 0.070
10.59 1.656 0.314 0.079
12.36 2.186 0.413 0.103
14.12 2.752 0.525 0.131
15.89 3.442 0.648 0.162
17.66 4.166 0.783 0.195
19.42 - 0.929 0.231
21.19 - 0.744 0.270
22.95 - 0.858 0.312
24.72 - 0.980 0.356
28.25 - 1.244 0.453
31.78 - 1.537 0.560
35.31 - 1.858 0.677
38.84 - 2.205 0.804
42.37 - 2.581 0.941
45.90 - 2.982 1.088
49.43 - 3.411 1.245
52.97 - 4.249 1.411
56.50 - - 1.587
60.03 - - 1.772
63.56 - - 1.967
67.09 - - 2.174
70.62 - - 2.385
79.45 - - 2.959
88.28 - - 3.589


For SI units: 1 standard cubic foot per minute = 28.32 SLPM, 1 inch = 25 mm, 1 foot = 304.8 mm, 1 pound-force per square inch = 6.8947 kPa

Notes:
  • 1 Based on the pressure of 14.7 psig (101 kPa) at 68°F (20°C).
  • 2 Based on the pressure of 55 psig (379 kPa) at 68°F (20°C).


TABLE 1310.2.1(5)
PRESSURE LOSS FOR OXYGEN
FLOW RATE (SCFM)1 PRESSURE DROP (psi) PER 100 FEET2
1/2 INCH PIPE 3/4 INCH PIPE 1 INCH PIPE
0.35 0.004 - -
0.71 0.013 0.003 -
1.06 0,025 0.005 -
1.41 0.041 0.008 -
1.77 0.060 0.012 -
2.12 0.082 0.016 -
2.47 0.107 0.021 -
2.82 0.135 0.026 -
3.18 0.166 0.032 -
3.53 0.199 0.038 -
4.24 0.274 0.053 -
4.94 0.359 0.069 -
5.65 0.454 0.087 -
6.36 0.558 0.107 -
7.06 0.672 0.129 0.033
7.77 0.795 0.153 0.039
8.47 0.927 0.179 0.045
9.18 1.066 0.205 0.052
9.89 1.218 0.233 0.059
10.59 1.377 0.263 0.066
12.36 1.811 0.346 0.087
14.12 2.298 0.438 0.110
15.89 2.837 0.539 0.135
17.66 3.456 0.650 0.163
19.42 - 0.771 0.193
21.19 - 0.900 0.225
22.95 - 1.038 0.260
24.72 - 1.185 0.295
28.25 - 1.505 0.375
31.78 - 1.859 0.463
35.31 - 2.247 0.559
38.84 - 2.667 0.663
42.37 - 3.121 0.775
45.90 - 3.607 0.895
49.43 - 4.125 1.022
52.97 - - 1.157
56.50 - - 1.299
60.03 - - 1.449
63.56 - - 1.607
67.09 - - 1.772
70.62 - - 1.944
81.21 - - 2.503
91.81 - - 3.127
102.40 - - 3.813


For SI units: 1 standard cubic foot per minute = 28.32 SLPM, 1 inch = 25 mm, 1 foot = 304.8 mm, 1 pound-force per square inch = 6.8947 kPa

Notes:
  • 1 Based on the pressure of 14.7 psig (101 kPa) at 68°F (20°C).
  • 2 Based on the pressure of 55 psig (379 kPa) at 68°F (20°C).


TABLE 1310.2.1(6)
PRESSURE LOSS FOR VACUUM
FLOW RATE (SCFM)1 VACUUM LOSS (inch of mercury)
PER 100 FEET FOR COPPER TUBE2
3/4 INCH TUBE 1 INCH TUBE 11/4 INCH TUBE 11/2 INCH TUBE 2 INCH TUBE
0.35 0.019 - - - -
0.71 0.061 - - - -
1.06 0.120 - - - -
1.41 0.194 - - - -
1.77 0.284 - - - -
2.12 0.387 - - - -
2.47 0.504 - - - -
2.82 0.634 - - - -
3.18 0.777 - - - -
3.53 0.932 0.238 - - -
4.24 1.277 0.325 - - -
4.94 1.669 0.424 - - -
5.65 2.106 0.534 - - -
6.36 2.586 0.655 - - -
7.06 3.110 0.787 0.272 - -
7.77 3.674 0.929 0.321 - -
8.47 4.280 1.081 0.373 - -
9.18 4.927 1.243 0.429 - -
9.89 - 1.416 0.488 - -
10.59 - 1.597 0.551 0.242 -
11.30 - 1.789 0.616 0.270 -
12.01 - 1.990 0.685 0.300 -
12.71 - 2.200 0.757 0.332 -
13.42 - 2.419 0.832 0.365 -
14.12 - 2.648 0.911 0.399 -
14.83 - 2.886 0.992 0.435 -
15.54 - 3.132 1.077 0.471 -
16.24 - 3.388 1.164 0.510 -
16.95 - 3.652 1.254 0.549 -
17.66 - 3.925 1.348 0.590 -
18.36 - 4.207 1.444 0.632 0.167
19.07 - 4.498 1.543 0.675 0.179
19.77 - 4.797 1.646 0.720 0.190
20.48 - - 1.751 0.766 0.202
21.19 - - 1.859 0.813 0.214
24.72 - - 2.441 1.066 0.281
28.25 - - 3.092 1.350 0.356
31.78 - - 3.811 1.662 0.438
35.31 - - 4.596 2.004 0.527
38.84 - - - 2.373 0.624
42.37 - - - 2.770 0.728
45.90 - - - 3.194 0.838
49.43 - - - 3.645 0.956
52.97 - - - 4.122 1.081
56.50 - - - 4.626 1.212
63.56 - - - - 1.495
70.62 - - - - 1.803
77.68 - - - - 2.138
84.74 - - - - 2.497
91.81 - - - - 2.882
98.87 - - - - 3.291
105.93 - - - - 3.724
112.99 - - - - 4.181


For SI units: 1 standard cubic foot per minute = 28.32 SLPM, 1 inch = 25 mm, 1 foot = 304.8 mm, 1 inch of mercury = 3.386 kPa

Notes:
  • 1 Based on the pressure of 14.7 psig (101 kPa) at 68°F (20°C).
  • 2 Based on the pressure of 19 inches of mercury gauge vacuum (64 kPa) at 68°F (20°C).


TABLE 1310.2.1(7)
PRESSURE LOSS FOR VACUUM (CATEGORY 3)
FLOW RATE (SCFM)1 VACUUM LOSS (inch of mercury)
PER 100 FEET FOR COPPER TUBE2
3/4 INCH TUBE 1 INCH TUBE 11/4 INCH TUBE 11/2 INCH TUBE 2 INCH TUBE
0.35 0.005 - - - -
0.71 0.010 - - - -
1.06 0.015 - - - -
1.41 0.021 - - - -
1.77 0.026 - - - -
2.12 0.060 0.010 - - -
2.47 0.077 0.020 - - -
2.82 0.096 0.025 - - -
3.18 0.118 0.031 0.011 - -
3.53 0.141 0.036 0.013 - -
4.24 0.192 0.050 0.017 - -
4.94 0.249 0.064 0.023 0.010 -
5.65 0.313 0.081 0.028 0.012 -
6.36 0.383 0.099 0.035 0.015 -
7.06 0.459 0.118 0.041 0.018 -
7.77 0.541 0.139 0.049 0.021 -
8.47 0.628 0.161 0.056 0.024 -
9.18 0.722 0.185 0.065 0.027 -
9.89 0.821 0.210 0.073 0.031 -
10.59 0.925 0.237 0.083 0.035 -
11.30 1.035 0.265 0.092 0.039 0.010
12.01 1.151 0.294 0.102 0.043 0.011
12.71 1.270 0.324 0.113 0.048 0.012
13.42 1.396 0.356 0.124 0.052 0.014
14.12 1.525 0.389 0.135 0.057 0.015
14.83 1.662 0.424 0.147 0.062 0.016
15.54 1.803 0.460 0.160 0.068 0.017
16.24 1.948 0.496 0.172 0.073 0.019
16.95 2.099 0.535 0.186 0.078 0.020
17.66 2.256 0.574 0.199 0.084 0.022
18.36 2.415 0.615 0.213 0.090 0.023
19.07 2.581 0.657 0.228 0.096 0.025
19.77 2.750 0.699 0.243 0.102 0.026
20.48 2.925 0.744 0.258 0.109 0.028
21.19 3.106 0.790 0.274 0.115 0.030
24.72 4.074 1.034 0.358 0.151 0.039
28.25 - 1.307 0.452 0.190 0.049
31.78 - 1.608 0.556 0.234 0.060
35.31 - 1.936 0.669 0.281 0.072
38.84 - 2.291 0.791 0.332 0.085
42.37 - 2.672 0.922 0.387 0.099
45.90 - 3.078 1.062 0.446 0.113
49.43 - 3.510 1.211 0.508 0.129
52.97 - 3.969 1.368 0.574 0.146
56.50 - 4.450 1.534 0.643 0.163
63.56 - - 1.890 0.792 0.201
70.62 - - 2.278 0.954 0.242
77.68 - - 2.699 1.130 0.286
84.74 - - 3.151 1.318 0.334
91.81 - - 3.634 1.520 0.385
98.87 - - 4.148 1.734 0.439
105.93 - - 4.691 1.961 0.496
112.99 - - - 2.200 0.556


For SI units: 1 standard cubic foot per minute = 28.32 SLPM, 1 inch = 25 mm, 1 foot = 304.8 mm, 1 inch of mercury = 3.386 kPa

Notes:
  • 1 Based on the pressure of 14.7 psig (101 kPa) at 68°F (20°C).
  • 2 Based on the pressure of 19 inches of mercury gauge vacuum (64 kPa) at 68°F (20°C).

Related Code Sections


1310.2.1 Health Care Facilities and Medical Gas and Medical Vacuum Systems, Mains and Branches
Mains and branches in medical gas piping systems shall be not less than DN15 (NPS 1 / 2 ) ( 5 / 8 inch O.D.) size. Mains and branches in medical ...
California Plumbing Code 2019 > 13 Health Care Facilities and Medical Gas and Medical Vacuum Systems > 1310.0 Installation of Piping > 1310.2 Required Pipe Sizing > 1310.2.1 Mains and Branches
613.6 Water Supply and Distribution,
water outlet. Nonrecirculated fixture branch piping shall not exceed 25 feet (7.62 meters) in length. Dead-end piping (risers with no flow, branches ...
California Plumbing Code 2016 > 6 Water Supply and Distribution > 613.0 [OSHPD 1, 2, 3 & 4] Domestic Hot-Water Distribution Systems for Health Facilities and Clinics > 613.6
613.6 Water Supply and Distribution,
water outlet. Non-recirculated fixture branch piping shall not exceed 25 feet (7.62 meters) in length. Dead-end piping (risers with no flow, branches ...
California Plumbing Code 2019 > 6 Water Supply and Distribution > 613.0 [OSHPD 1, 1R, 2, 3, 4 & 5] Domestic Hot-Water Distribution Systems for Health Facilities and Clinics > 613.6
614.1 Water Supply and Distribution,
Branches to dialysis machines shall be 1 / 4 inch (6.4 mm) inside dimension and take off from the bottom of the main feedline. Branch lines may be PFA ...
California Plumbing Code 2019 > 6 Water Supply and Distribution > 614.0 Dialysis Water-Distribution Systems > 614.1
Help Contact Us Privacy Terms
Code sheet exports
Code sheet exports
Generate a code sheet that integrates with your drawing set.
Code Compare
Code Compare
Highlight differences between any two building codes.
Code diagrams
Code diagrams
Unpack the code through illustrations and descriptions.
Code Calculators
Code Calculators
Code calculators automatically generate a detailed list of requirements.
Search
Search
Don't miss relevant code. Quickly locate sections across your jurisdiction.
Shared projects
Shared projects
Projects provide a dedicated space to collaborate on code research.
UpCodes Premium
Leverage the most sophisticated code compliance platform.
TRY FREE FOR TWO WEEKS VISIT PRICING
UpCodes Premium
Leverage the full code compliance platform.
START 2 WEEK FREE TRIAL LEARN MORE