1312.3 Main Valves
JUMP TO FULL CODE CHAPTER
A shutoff valve shall be provided in the main supply line inside of the building, except where
one or more of the following conditions exist:
- The source and source valve are located inside the building served.
- The source system is physically mounted to the wall of the building served, and the pipeline enters the building in the immediate vicinity of the source valve. [NFPA 99:5.1.4.5]
The main line valve shall be located to permit access by authorized personnel only. [NFPA 99:5.1.4.5.1]
Related Code Sections
1312.3 Health Care Facilities and Medical Gas and Medical Vacuum Systems, Main Valves
A shutoff valve shall be provided in the main supply line inside of the building, except where
one or more of the following conditions exist:
The ...
California Plumbing Code 2016 > 13 Health Care Facilities and Medical Gas and Medical Vacuum Systems > 1312.0 Shutoff Valves > 1312.3 Main Valves
1311.10.3 Health Care Facilities and Medical Gas and Medical Vacuum Systems, Main Line Valves
Main line valves shall be labeled in substance as follows:
MAIN LINE VALVE FOR THE (GAS/VACUUM NAME) SERVING (NAME OF BUILDING)
[NFPA 99 ...
California Plumbing Code 2019 > 13 Health Care Facilities and Medical Gas and Medical Vacuum Systems > 1311.0 Valves > 1311.10 Identification of Shutoff Valves > 1311.10.3 Main Line Valves
1112.5 Refrigeration, Actuation
, and the main valve shall
open automatically at the set pressure and, where an essential
part of the pilot fails, shall discharge its full rated capacity ...
California Mechanical Code 2016 > 11 Refrigeration > 1112.0 Pressure-Relief Devices > 1112.5 Actuation
1112.6 Refrigeration, Actuation
, and the main valve shall open automatically at the set pressure and, where an essential part of the pilot fails, shall discharge its full rated capacity ...
California Mechanical Code 2019 > 11 Refrigeration > 1112.0 Pressure-Relief Devices > 1112.6 Actuation
1006.0 Boilers and Pressure Vessels, Shutoff Valves
An approved manual shutoff valve shall be installed upstream of all control devices on the main burner
of a gas-fired boiler. The takeoff point ...