Section E4004 Luminaire Installation
JUMP TO FULL CODE CHAPTER
In a completed installation, each outlet box shall be provided with a cover except where covered by means of a luminaire canopy, lampholder or device with a faceplate. (410.22)
Combustible wall or ceiling finish exposed between the inside edge of a luminaire canopy or pan and the outlet box and having a surface area of 180 in.2 (116 129 mm2) or more shall be covered with a noncombustible material. (410.23)
Luminaires shall be installed so that the connections between the luminaire conductors and the circuit conductors can be accessed without requiring the disconnection of any part of the wiring. Luminaires that are connected by attachment plugs and receptacles meet the requirement of this section. (410.8)
Luminaires and lampholders shall be securely supported. A luminaire that weighs more than 6 pounds (2.72 kg) or exceeds 16 inches (406 mm) in any dimension shall not be supported by the screw shell of a lampholder. [410.30(A)]
Luminaires having exposed ballasts, transformers, LED drivers or power supplies shall be installed so that such ballasts, transformers, LED drivers or power supplies are not in contact with combustible material unless listed for such condition. [410.136(A)]
Where a surface-mounted luminaire containing a ballast, transformer, LED driver or power supply is installed on combustible low-density cellulose fiberboard, the luminaire shall be marked for this purpose or it shall be spaced not less than 11/2 inches (38 mm) from the surface of the fiberboard. Where such luminaires are partially or wholly recessed, the provisions of Sections E4004.8 and E4004.9 shall apply. [410.136(B)]
A recessed luminaire that is not identified for contact with insulation shall have all recessed parts spaced at least 1/2 inch (12.7 mm) from combustible materials. The points of support and the finish trim parts at the opening in the ceiling, wall or other finished surface shall be permitted to be in contact with combustible materials. A recessed luminaire that is identified for contact with insulation, Type IC, shall be permitted to be in contact with combustible materials at recessed parts, points of support, and portions passing through the building structure and at finish trim parts at the opening in the ceiling or wall. [410.116(A)(1) and (A)(2)]
Thermal insulation shall not be installed above a recessed luminaire or within 3 inches (76 mm) of the recessed luminaire's enclosure, wiring compartment, ballast, transformer, LED driver or power supply except where such luminaire is identified for contact with insulation, Type IC. [410.116(B)]
Related Code Sections
Section E4004 Devices and Luminaires, Luminaire Installation
In a completed installation, each outlet box shall be provided with a cover except where covered by means of a luminaire canopy, lampholder or device ...
Section E4004 Devices and Luminaires, Luminaire Installation
In a completed installation, each outlet box shall be provided with a cover except where covered by means of a luminaire canopy, lampholder or device ...
E4004.2 Devices and Luminaires, Combustible Material at Outlet Boxes
Combustible wall or ceiling finish exposed between the inside edge of a luminaire canopy or pan and the outlet box to which the luminaire connects ...
2012 Virginia Residential Code > 40 Devices and Luminaires > E4004 Luminaire Installation > E4004.2 Combustible Material at Outlet Boxes
E4004.3 Devices and Luminaires, Access
Luminaires shall be installed so that the connections between the luminaire conductors and the circuit conductors can be accessed without requiring ...
2015 Virginia Residential Code > 40 Devices and Luminaires > E4004 Luminaire Installation > E4004.3 Access
E4004.3 Devices and Luminaires, Access
Luminaires shall be installed so that the connections between the luminaire conductors and the circuit conductors can be accessed without requiring ...
2012 Virginia Residential Code > 40 Devices and Luminaires > E4004 Luminaire Installation > E4004.3 Access