1609.1.1.2.2 Lower Limits on Components and Cladding
JUMP TO FULL CODE CHAPTER
The design pressures for components and cladding on walls or roofs shall be selected as the greater of the wind tunnel test results or 80 percent of the pressure obtained for Zone 4 for walls and Zone 1 for roofs as determined in Section 6.5 of ASCE 7, unless specific testing is performed that demonstrates it is the aerodynamic coefficient of the building, rather than shielding from nearby structures, that is responsible for the lower values. Alternatively, limited tests at a few wind directions without specific adjacent buildings, but in the presence of an appropriate upwind roughness, shall be permitted to be used to demonstrate that the lower pressures are due to the shape of the building and not to shielding.
Related Code Sections
1609.1.1.2.2 Structural Design, Lower Limits on Components and Cladding
The design pressures for components and cladding on walls or roofs shall be selected as the greater of the wind tunnel test results or 80 percent ...
Ohio Building Code 2011 > 16 Structural Design > 1609 Wind Loads > 1609.1 Applications > 1609.1.1 Determination of Wind Loads > 1609.1.1.2 Wind Tunnel Test Limitations > 1609.1.1.2.2 Lower Limits on Components and Cladding
1609.6.4.4.1 Structural Design, Components and Cladding
Wind pressure for each component or cladding element is applied as follows using C net values based on the effective wind area, A , contained ...
Ohio Building Code 2017 > 16 Structural Design > 1609 Wind Loads > 1609.6 Alternate All-Heights Method > 1609.6.4 Design Procedure > 1609.6.4.4 Application of Wind Pressures > 1609.6.4.4.1 Components and Cladding
1707.6 Structural Tests and Special Inspections, Architectural Components
Periodic special inspection during the erection and fastening of exterior cladding, interior and exterior nonbearing walls and interior and exterior ...
Ohio Building Code 2011 > 17 Structural Tests and Special Inspections > 1707 Special Inspections Forseismic Resistance > 1707.6 Architectural Components
1705.12.5 Special Inspections and Tests, Architectural Components
Periodic special inspection is required for the erection and fastening of exterior cladding, interior and exterior nonbearing walls and interior ...
Ohio Building Code 2017 > 17 Special Inspections and Tests > 1705 Required Special Inspections and Tests > 1705.12 Special Inspections for Seismic Resistance > 1705.12.5 Architectural Components
1706.4 Structural Tests and Special Inspections, Wind-Resisting Components
Periodic special inspection is required for the following systems and components: Roof cladding. Wall cladding ...
Ohio Building Code 2011 > 17 Structural Tests and Special Inspections > 1706 Special Inspections Forwind Requirements > 1706.4 Wind-Resisting Components