// CODE SNIPPET
4.3.1.5 Low-Piled Storage
Go To Full Code Chapter
4.3.1.5.1
For storage of Class I through Class IV commodities 12 ft (3.7 m) or less in height that do not meet the definition of Miscellaneous Storage that is on solid shelf racks, in-rack sprinklers shall be provided in accordance with 25.6.1, and ceiling sprinkler protection shall be provided in accordance with this chapter for the applicable occupancy hazard criteria.
4.3.1.5.2
For storage of Group A plastic commodities 5 ft (1.5 m) or less in height that do not meet the definition of Miscellaneous Storage that is on solid shelf racks, in-rack sprinklers shall be provided in accordance with 25.6.1, and ceiling sprinkler protection shall be provided in accordance with this chapter for the applicable occupancy hazard criteria.
Upcodes Diagrams
Related Code Sections
3.3.118* Definitions, Low-Piled Storage
Solid-piled, palletized, rack storage, bin box, and shelf storage up to 12 ft (3.7 m) in height ...
3.9.1.17* Definitions, Low-Piled Storage
Solid-piled, palletized, rack storage, bin box, and shelf storage up to 12 ft (3.7 m) in height ...
4.3.1.5 General Requirements, Low-Piled Storage
For storage of Class I through Class IV commodities 12 ft (3.7 m) or less in height that do not meet the definition of Miscellaneous Storage ...
25.2.2 Protection of Rack Storage Using In-Rack Sprinklers, Miscellaneous and Low-Piled Storage
are installed in accordance with Sections 25.4 through 25.7 to protect low-piled rack storage that does not meet the definition of miscellaneous storage ...