4.3.1.5.1
For storage of Class I through Class IV commodities 12 ft (3.7 m) or less in height that do not meet the definition of Miscellaneous Storage that is on solid shelf racks, in-rack sprinklers shall be provided in accordance with 25.6.1, and ceiling sprinkler protection shall be provided in accordance with this chapter for the applicable occupancy hazard criteria.
4.3.1.5.2
For storage of Group A plastic commodities 5 ft (1.5 m) or less in height that do not meet the definition of Miscellaneous Storage that is on solid shelf racks, in-rack sprinklers shall be provided in accordance with 25.6.1, and ceiling sprinkler protection shall be provided in accordance with this chapter for the applicable occupancy hazard criteria.