R602.10.2.2 Locations of Braced Wall Panels
JUMP TO FULL CODE CHAPTER
A braced wall panel shall begin within 10 feet (3810 mm) from each end of a braced wall line as determined in Section R602.10.1.1. The distance between adjacent edges of braced wall panels along a braced wall line shall be not greater than 20 feet (6096 mm) as shown in Figure R602.10.2.2.

For SI: 1 foot = 304.8 mm.
LOCATION OF BRACED WALL PANELS
Exception: Braced wall panels constructed of Method WSP or BV-WSP and continuous sheathing methods as specified in Section R602.10.4 shall be permitted to begin not more than 10 feet (3048 mm) from each end of a braced wall line provided that each end complies with one of the following:
- A minimum 24-inch-wide (610 mm) panel for Methods WSP, CS-WSP, CS-G and CS-PF is applied to each side of the building corner as shown in End Condition 4 of Figure R602.10.7.
- The end of each braced wall panel closest to the end of the braced wall line shall have an 1,800 lb (8 kN) hold-down device fastened to the stud at the edge of the braced wall panel closest to the corner and to the foundation or framing below as shown in End Condition 5 of Figure R602.10.7.
Related Code Sections
R602.10.2.2 Wall Construction, Locations of Braced Wall Panels
For SI: 1 foot = 304.8 mm.
FIGURE R602.10.2.2
LOCATION OF BRACED WALL PANELS ...
Residential Code 2018 of Kansas > 6 Wall Construction > R602 Wood Wall Framing > R602.10 Wall Bracing > R602.10.2 Braced Wall Panels > R602.10.2.2 Locations of Braced Wall Panels
R106.1.3 Scope and Administration, Information on Braced Wall Design
on the construction documents. Pertinent information including, but not limited to, bracing methods, location and length of braced wall panels ...
Residential Code 2018 of Kansas > 1 Scope and Administration > R106 Construction Documents > R106.1 Submittal Documents > R106.1.3 Information on Braced Wall Design
2308.6.2 Wood, Braced Wall Panels
2308.6.3(1). A braced wall panel shall be located at each end of the braced wall line and at the corners of intersecting braced wall lines or shall ...
Building Code 2018 of Kansas > 23 Wood > 2308 Conventional Light-Frame Construction > 2308.6 Wall Bracing > 2308.6.2 Braced Wall Panels
R502.2.1 Floors, Framing at Braced Wall Lines
A load path for lateral forces shall be provided between floor framing and braced wall panels located above or below a floor, as specified ...
Residential Code 2018 of Kansas > 5 Floors > R502 Wood Floor Framing > R502.2 Design and Construction > R502.2.1 Framing at Braced Wall Lines