Refrigerant piping crossing an open space that affords passageway in a building shall be not less than 7.25 feet (2210 mm) above the floor unless the piping is located against the ceiling of such space and is permitted by the Authority Having Jurisdiction. [ASHRAE 15:8.10.1]
1109.4.1 Protection From Mechanical Damage
Passages shall not be obstructed by refrigerant piping. Refrigerant piping shall not be located in an elevator, dumbwaiter, or other shaft containing a moving object, or in a shaft that has openings to living quarters, or to means of egress. Refrigerant piping shall not be installed in an enclosed public stairway, stair landing, or means of egress. [ASHRAE 15:8.10.2]

Related Code Sections

1109.4 Refrigeration, Location of Refrigeration Piping
Refrigerant piping crossing an open space that affords passageway in a building shall be not less than 7.25 feet (2210 mm) above the floor unless ...
1106.1.4 Refrigeration, A1 Refrigerant
containing less than 300 pounds (136.1 kg) of refrigerant R-123 and located in an approved exterior location. Refrigeration machinery rooms shall ...