3504.2.1 Location of Outdoor Storage Areas
JUMP TO FULL CODE CHAPTER
Outdoor storage areas for flammable gases shall be located at or above grade level, and in accordance with FC3504.2.1.1 and FC Table 3504.2.1, as applicable.
FC TABLE 3504.2.1 FLAMMABLE GASES DISTANCE FROM OUTDOOR STORAGE AREAS TO EXPOSURES
FC TABLE 3504.2.1 FLAMMABLE GASES DISTANCE FROM OUTDOOR STORAGE AREAS TO EXPOSURES
TYPE OF OUTDOOR EXPOSURE | FLAMMABLE GAS STORAGE AREA MORE THAN 1500 SCF UP TO MAXIMUM 3500 SCF MINIMUM DISTANCE TO OUTDOOR EXPOSURE (FEET) |
Building or structure of combustible construction | 10a |
Building or structure of noncombustible construction | 5a |
Building openings | 10 |
Flammable and combustible liquids Aboveground — 1,000 gallons or less | 10a |
Flammable and combustible liquids Aboveground — in excess of 1,000 gallons | 20a |
Flammable and combustible liquids Underground tank — 1,000gallons or less | 10a |
Flammable and combustible liquids Underground tank — 1,000 gallons or less Vent or fill opening of tank | 15a |
Flammable and combustible liquids Underground tank — in excess of 1,000 gallons | 15a |
Flammable and combustible liquids Underground tank — in excess of 1,000 gallons Vent or fill opening of tank | 15a |
Flammable gas storage area, any pressure 1,500 SCF or less | 10a |
Flammable gas storage area, any pressure More than 1,500 SCF up to maximum 3,500 SCF | 20a |
Oxygen storage — 20,000 SCF or less | In accordance with NFPA 51a |
Oxygen storage — in excess of 20,000 SCF | In accordance with NFPA 55 a |
Combustible material or combustible waste | 10a |
Air compressor intakes or inlets to ventilating or air-conditioning equipment | 5 |
Group A occupancies and public gathering places | 25 |
Public sidewalks and parked motor vehicles | 10 |
Public streets, private roads and lot lines | 10a |
For SI: 1 foot = 304.8 mm, 1 cubic foot = 0.02832 m3, 1 gallon = 3.785 L. |
a. The minimum required distances shall be reduced to 5 feet when protective structures having a minimum fire-resistance rating of 2 hours interrupt the line of sight between the container and the exposure. The protective structure shall be at least 5 feet from the exposure. The configuration of the protective structure shall be designed to allow natural ventilation to prevent the accumulation of hazardous gas concentrations. |
Storage shall not be located where the stored flammable gases would be exposed to the following hazards in the event of the failure of their structure or containment systems:
- Electric power lines.
- Piping containing flammable or combustible liquids.
- Piping containing flammable gases.
- Piping containing oxidizing materials.
Related Code Sections
414.2.4 Special Detailed Requirements Based on Use and Occupancy, Hazardous Material in Group M Display and Storage Areas and in Group S Storage Areas
of a Group M or S occupancy or an outdoor control area is permitted to exceed the maximum allowable quantities per control area specified in Tables 307.7 ...
NYC Building Code 2008 > 4 Special Detailed Requirements Based on Use and Occupancy > 414 Hazardous Materials > 414.2 Control Areas > 414.2.4 Hazardous Material in Group M Display and Storage Areas and in Group S Storage Areas
414.6 Special Detailed Requirements Based on Use and Occupancy, Outdoor Storage, Dispensing and Use
storage or use areas, such areas shall be considered outdoor storage or use when the weather protection structure complies with Sections 414.6.1.1 ...
NYC Building Code 2014 > 4 Special Detailed Requirements Based on Use and Occupancy > 414 Hazardous Materials > 414.6 Outdoor Storage, Dispensing and Use
415.7.2 Special Detailed Requirements Based on Use and Occupancy, Flammable and Combustible Liquids
Where the storage tank area is located in a building of two or more occupancies, and the quantity of liquid exceeds the maximum allowable quantity ...
NYC Building Code 2008 > 4 Special Detailed Requirements Based on Use and Occupancy > 415 Groups H-1, H-2, H-3, H-4 and H-5 > 415.7 Group H-2 > 415.7.2 Flammable and Combustible Liquids
415.6.2 Special Detailed Requirements Based on Use and Occupancy, Flammable and Combustible Liquids
Where the storage tank area is located in a building of two or more ...
NYC Building Code 2014 > 4 Special Detailed Requirements Based on Use and Occupancy > 415 Groups H-1, H-2, H-3, H-4 and H-5 > 415.6 Group H-2 > 415.6.2 Flammable and Combustible Liquids
424.9 Special Detailed Requirements Based on Use and Occupancy, Storage Rooms
6 changes of air per hour and vents to the outdoors. Each entrance to the storage room shall be provided with a minimum 1 1 / 2 -hour rated self ...
NYC Building Code 2014 > 4 Special Detailed Requirements Based on Use and Occupancy > 424 Nonproduction Chemical Laboratories > 424.9 Storage Rooms