905.3.3.2 Location of Hose Connections
JUMP TO FULL CODE CHAPTER
Hose connections shall be provided in accordance with Section 905.4 and at each of the following locations:
- Within the mall at the entrance to each exit passageway or exit.
- At each floor-level landing within enclosed stairways opening directly on the mall.
- At exterior public entrances to the mall.
- At other locations as necessary so that the distance to reach all portions of a tenant space does not exceed 150 feet (45 720 mm) from a hose connection.
Related Code Sections
905.3.3.2 Fire Protection Systems, Location of Hose Connections
Hose connections shall be provided in accordance with Section 905.4 and at each of the following locations: 1. Within the mall ...
NYC Building Code 2008 > 9 Fire Protection Systems > 905 Standpipe Systems > 905.3 Required Installations > 905.3.3 Covered Mall Buildings > 905.3.3.2 Location of Hose Connections
905.3.3.2 Fire Protection Systems, Location of Hose Connections
Hose connections shall be provided in accordance with Section 905.4 and at each of the following locations: Within the mall at the entrance to each ...
NYC Building Code 2014 > 9 Fire Protection Systems > 905 Standpipe Systems > 905.3 Required Installations > 905.3.3 Covered Mall Buildings > 905.3.3.2 Location of Hose Connections
905.5 Fire Protection Systems, Location of Class II Standpipe Hose Connections
Class II standpipe hose connections shall be accessible and located in accordance with Section 905.3.4 ...
NYC Building Code 2014 > 9 Fire Protection Systems > 905 Standpipe Systems > 905.5 Location of Class II Standpipe Hose Connections
905.5.1 Fire Protection Systems, Groups A-1 and A-2
In Group A-1 and A-2 occupancies with occupant loads of more than 1,000, hose connections shall be located on each side of any stage ...
NYC Building Code 2008 > 9 Fire Protection Systems > 905 Standpipe Systems > 905.5 Location of Class II Standpipe Hose Connections > 905.5.1 Groups A-1 and A-2
905.4.1 Fire Protection Systems, Protection
Risers and laterals of Class I standpipe systems not located within an enclosed stairway or pressurized enclosure shall be protected by a degree ...
NYC Building Code 2008 > 9 Fire Protection Systems > 905 Standpipe Systems > 905.4 Location of Class I Standpipe Hose Connections > 905.4.1 Protection