Article 3 Location of Exits

Go To Full Code Chapter
§27-361 Arrangement
All exits and access facilities shall be located so that they are clearly visible, or their locations clearly indicated, and they shall be kept readily accessible and unobstructed at all times.
§27-362 Tenant Spaces
When more than one tenant occupies a building or floor area, each tenant shall have direct access to the required number of exits without passing through premises occupied by other tenants, except as permitted for balconies in subdivision (g) of section 27-369 of article five of this subchapter.
§27-363 Remote Location
(a) When more than one exit is required from a floor of a building, each such required exit shall be placed as remote from the others as is practicable. Where this results in a distance between exits exceeding the maximum travel distances required by section 27-357, additional remote vertical exits shall be provided.

(b) In addition to the requirements of subdivision (a) of this section:

(1) For exits serving spaces classified in occupancy groups G or J-2, in no event shall such exits be less than fifteen feet distant from each other.

(2) For exits serving spaces classified in other occupancies, in no event shall such distance be less than thirty feet or one-third the maximum travel distance required by section 27-357, whichever is greater.

(c) On any floor containing ten thousand square feet or more in a high rise building classified in occupancy group E (office space), each exit that is required to be remote from another exit shall not share any common walls, floors, ceilings, scissor stair assemblies, or other enclosures.
§27-364 Exit Discharge
All vertical exits shall extend in a continuous enclosure to discharge directly, or by way of a yard, court, or exit passageway, to an open exterior space. When vertical exits serving floors above grade continue in the same enclosure to serve floors below grade, the portion of such vertical exits above grade shall be separated from the portion below grade by construction having at least a one hour fire-resistance rating, with three-quarter hour self-closing doors opening in the direction of exit travel from the floors below grade, except that buildings classified in residential occupancy group J-3 and educational occupancy group G shall be exempt from this requirement.

Related Code Sections

Article 3 Means of Egress, Location of Exits
All exits and access facilities shall be located so that they are clearly visible, or their locations clearly indicated, and they shall be kept ...
1023.3 Means of Egress, Exit Discharge Location
Exterior balconies, stairways and ramps shall be located at least 10 feet (3048 mm) from adjacent lot lines and from other buildings on the same lot ...
1027.3 Means of Egress, Exit Discharge Location
Exterior balconies, stairways and ramps shall be located at least 10 feet (3048 mm) from adjacent lot lines and from other buildings on the same lot ...