// CODE SNIPPET
240.24 Location in or on Premises
Go To Full Code Chapter
(A) Accessibility
Circuit breakers and switches containing fuses shall be readily accessible and installed so that the center of the grip of the operating handle of the switch or circuit breaker, when in its highest position, is not more than 2.0 m (6 ft 7 in.) above the floor or working platform, unless one of the following applies:
- For busways, as provided in 368.17(C).
- For supplementary overcurrent protection, as described in 240.10.
- For overcurrent devices, as described in 225.40 and 230.92.
- For overcurrent devices adjacent to utilization equipment that they supply, access shall be permitted to be by portable means.
Exception: The use of a tool shall be permitted to access overcurrent devices located within listed industrial control panels or similar enclosures.
(B) Occupancy
Each occupant shall have ready access to all overcurrent devices protecting the conductors supplying that occupancy, unless otherwise permitted in 240.24(B)(1) and (B)(2).
(1) Service and Feeder Overcurrent Devices
Where electric service and electrical maintenance are provided by the building management and where these are under continuous building management supervision, the service overcurrent devices and feeder overcurrent devices supplying more than one occupancy shall be permitted to be accessible only to authorized management personnel in the following:
- Multiple-occupancy buildings
- Guest rooms or guest suites
(2) Branch-Circuit Overcurrent Devices
Where electric service and electrical maintenance are provided by the building management and where these are under continuous building management supervision, the branch-circuit overcurrent devices supplying any guest rooms or guest suites without permanent provisions for cooking shall be permitted to be accessible only to authorized management personnel.
(C) Not Exposed to Physical Damage
Overcurrent devices shall be located where they will not be exposed to physical damage.
Informational Note: See 110.11, Deteriorating Agents.
(D) Not in Vicinity of Easily Ignitible Material
Overcurrent devices shall not be located in the vicinity of easily ignitible material, such as in clothes closets.
(E) Not Located in Bathrooms
In dwelling units, dormitory units, and guest rooms or guest suites, overcurrent devices, other than supplementary overcurrent protection, shall not be located in bathrooms.
(F) Not Located Over Steps
Overcurrent devices shall not be located over steps of a stairway.
Upcodes Diagrams
Related Code Sections
240.24 Wiring and Protection, Location in or on Premises
to be by portable means. Exception: The use of a tool shall be permitted to access overcurrent devices located within listed industrial control panels ...
240.24 Wiring and Protection, Location in or on Premises
to be by portable means. Exception: The use of a tool shall be permitted to access overcurrent devices located within listed industrial control panels ...
(A) Wiring and Protection, Accessibility
to be by portable means. Exception: The use of a tool shall be permitted to access overcurrent devices located within listed industrial control panels ...
(B) Wiring and Protection, Occupancy
Each occupant shall have ready access to all overcurrent devices protecting the conductors supplying that occupancy, unless otherwise permitted ...
(B) Wiring and Protection, Occupancy
Each occupant shall have ready access to all overcurrent devices protecting the conductors supplying that occupancy, unless otherwise permitted ...