517.7.4 Listing/Class
JUMP TO FULL CODE CHAPTER
Solid-fuel appliances (whether or
not under a hood) with fireboxes of 5 cubic feet (0.14 m3)
volume or less shall have not less than a listed 2-A rated water-spray fire extinguisher or a 1.6 gallon (6.1L) wet
chemical fire extinguisher listed for Class K fires in accordance
with NFPA 10 with a travel distance of not more
than 20 feet (6096 mm) to the appliance. [NFPA 96:14.7.8]
Related Code Sections
517.7.4 Exhaust Systems, Listing/Class
rated water-spray fire extinguisher or a 1.6 gallon (6.1 L)
wet chemical fire extinguisher listed for Class K fires in
accordance with NFPA 10 ...
California Mechanical Code 2016 > 5 Exhaust Systems > 517.0 Solid-Fuel Cooking Operations > 517.7 Fire-Extinguishing Equipment for Solid-Fuel Cooking > 517.7.4 Listing/Class
517.7.4 Exhaust Systems, Listing/Class
rated water-spray fire extinguisher or a 1.6 gallon (6.1L) wet
chemical fire extinguisher listed for Class K fires in accordance
with NFPA 10 ...
California Mechanical Code 2019 > 5 Exhaust Systems > 517.0 Solid-Fuel Cooking Operations > 517.7 Fire-Extinguishing Equipment for Solid-Fuel Cooking > 517.7.4 Listing/Class
906.4.2 Fire Protection and Life Safety Systems, Class K Portable Fire Extinguishers for Deep Fat Fryers
Where hazard areas include deep fat fryers, listed Class K portable fire extinguishers shall be provided as follows: For up to four fryers having ...
California Fire Code 2019 > 9 Fire Protection and Life Safety Systems > 906 Portable Fire Extinguishers > 906.4 Cooking Equipment Fires > 906.4.2 Class K Portable Fire Extinguishers for Deep Fat Fryers
H2.1 Hazardous Materials Management Plans and Hazardous Materials Inventory Statements, When Required
are stored. The hazardous materials inventory statement shall list, by hazard class, all hazardous materials stored. The hazardous materials ...
California Fire Code 2019 > H Hazardous Materials Management Plans and Hazardous Materials Inventory Statements > H2 Hazardous Materials Inventory Statements (HMIS) > H2.1 When Required
H2.1 Hazardous Materials Management Plans and Hazardous Materials Inventory Statements, When Required
are stored. The hazardous materials inventory statement shall list, by hazard class, all hazardous materials stored. The hazardous materials inventory ...
California Fire Code 2016 > H Hazardous Materials Management Plans and Hazardous Materials Inventory Statements > H2 Hazardous Materials Inventory Statements (HMIS) > H2.1 When Required