5705.3.6.2 Listed and Approved Machines
JUMP TO FULL CODE CHAPTER
Parts cleaning and degreasing conducted in listed and approved machines in accordance with Section 5705.3.6.1 shall be in accordance with Sections 5705.3.6.2.1 through 5705.3.6.2.7.
Solvents shall be classified and shall be compatible with the machines within which they are used.
The quantity of solvent shall not exceed the listed design capacity of the machine for the solvent being used with the machine.
Solvent quantities shall be limited as follows:
- Machines without remote solvent reservoirs shall be limited to quantities set forth in Section 5705.3.5.
- Machines with remote solvent reservoirs using Class I liquids shall be limited to quantities set forth in Section 5705.3.5.
- Machines with remote solvent reservoirs using Class II liquids shall be limited to 35 gallons (132 L) per machine. The total quantities shall not exceed an aggregate of 240 gallons (908 L) per control area in buildings not equipped throughout with an approved automatic sprinkler system and an aggregate of 480 gallons (1817 L) per control area in buildings equipped throughout with an approved automatic sprinkler system in accordance with Section 903.3.1.1.
- Machines with remote solvent reservoirs using Class IIIA liquids shall be limited to 80 gallons (303 L) per machine.
Work areas of machines with remote solvent reservoirs shall not be used for immersion soaking of parts.
Multiple machines shall be separated from each other by a distance of not less than 30 feet (9144 mm) or by a fire barrier with a minimum 1-hour fire-resistance rating.
Machines shall be located in areas adequately ventilated to prevent accumulation of vapors.
Machines shall be installed in accordance with their listings.
Related Code Sections
5705.3.6.2 Flammable and Combustible Liquids, Listed and Approved Machines
Parts cleaning and degreasing conducted in listed and approved machines in accordance with Section 5705.3.6.1 shall be in accordance ...
Fire Code 2021 of Colorado > 57 Flammable and Combustible Liquids > 5705 Dispensing, Use, Mixing and Handling > 5705.3 Use, Dispensing and Mixing Inside of Buildings > 5705.3.6 Cleaning With Flammable and Combustible Liquids > 5705.3.6.2 Listed and Approved Machines
5705.3.6.2 Flammable and Combustible Liquids, Listed and Approved Machines
Parts cleaning and degreasing conducted in listed and approved machines in accordance with Section 5705.3.6.1 shall be in accordance ...
Fire Code 2018 of Colorado > 57 Flammable and Combustible Liquids > 5705 Dispensing, Use, Mixing and Handling > 5705.3 Use, Dispensing and Mixing Inside of Buildings > 5705.3.6 Cleaning With Flammable and Combustible Liquids > 5705.3.6.2 Listed and Approved Machines
5705.3.6.2.7 Flammable and Combustible Liquids, Installation
Machines shall be installed in accordance with their listings ...
Fire Code 2018 of Colorado > 57 Flammable and Combustible Liquids > 5705 Dispensing, Use, Mixing and Handling > 5705.3 Use, Dispensing and Mixing Inside of Buildings > 5705.3.6 Cleaning With Flammable and Combustible Liquids > 5705.3.6.2 Listed and Approved Machines > 5705.3.6.2.7 Installation
5705.3.6.2.1 Flammable and Combustible Liquids, Solvents
Solvents shall be classified and shall be compatible with the machines within which they are used ...
Fire Code 2021 of Colorado > 57 Flammable and Combustible Liquids > 5705 Dispensing, Use, Mixing and Handling > 5705.3 Use, Dispensing and Mixing Inside of Buildings > 5705.3.6 Cleaning With Flammable and Combustible Liquids > 5705.3.6.2 Listed and Approved Machines > 5705.3.6.2.1 Solvents
5705.3.6.2.1 Flammable and Combustible Liquids, Solvents
Solvents shall be classified and shall be compatible with the machines within which they are used ...
Fire Code 2018 of Colorado > 57 Flammable and Combustible Liquids > 5705 Dispensing, Use, Mixing and Handling > 5705.3 Use, Dispensing and Mixing Inside of Buildings > 5705.3.6 Cleaning With Flammable and Combustible Liquids > 5705.3.6.2 Listed and Approved Machines > 5705.3.6.2.1 Solvents