5704.3.4.4 Liquids for Maintenance and Operation of Equipment
JUMP TO FULL CODE CHAPTER
In all occupancies, quantities of flammable and combustible liquids in excess of 10 gallons (38 L) used for maintenance purposes and the operation of equipment shall be stored in liquid storage cabinets in accordance with Section 5704.3.2. Quantities not exceeding 10 gallons (38 L) are allowed to be stored outside of a cabinet where in approved containers located in private garages or other approved locations.
Related Code Sections
5704.3.4.4 Flammable and Combustible Liquids, Liquids for Maintenance and Operation of Equipment
In all occupancies, quantities of flammable and combustible liquids in excess of 10 gallons (38 L) used for maintenance purposes and the operation ...
California Fire Code 2019 > 57 Flammable and Combustible Liquids > 5704 Storage > 5704.3 Container and Portable Tank Storage > 5704.3.4 Quantity Limits for Storage > 5704.3.4.4 Liquids for Maintenance and Operation of Equipment
5704.3.4.4 Flammable and Combustible Liquids, Liquids for Maintenance and Operation of Equipment
In all occupancies, quantities of flammable and combustible liquids in excess of 10 gallons (38 L) used for maintenance purposes and the operation ...
California Fire Code 2016 > 57 Flammable and Combustible Liquids > 5704 Storage > 5704.3 Container and Portable Tank Storage > 5704.3.4 Quantity Limits for Storage > 5704.3.4.4 Liquids for Maintenance and Operation of Equipment
6303.1.1.2 Oxidizers, Oxidizing Gases and Oxidizing Cryogenic Fluids, Class 3 Liquid and Solid Oxidizers
are necessary for maintenance purposes or operation of equipment. The oxidizers shall be stored in approved containers and in an approved manner ...
California Fire Code 2019 > 63 Oxidizers, Oxidizing Gases and Oxidizing Cryogenic Fluids > 6303 General Requirements > 6303.1 Quantities Not Exceeding the Maximum Allowable Quantity Per Control Area > 6303.1.1 Special Limitations for Indoor Storage and Use by Occupancy > 6303.1.1.2 Class 3 Liquid and Solid Oxidizers
6303.1.1.2 Oxidizers, Oxidizing Gases and Oxidizing Cryogenic Fluids, Class 3 Liquid and Solid Oxidizers
are necessary for maintenance purposes or operation of equipment. The oxidizers shall be stored in approved containers and in an approved manner ...
California Fire Code 2016 > 63 Oxidizers, Oxidizing Gases and Oxidizing Cryogenic Fluids > 6303 General Requirements > 6303.1 Quantities Not Exceeding the Maximum Allowable Quantity Per Control Area > 6303.1.1 Special Limitations for Indoor Storage and Use by Occupancy > 6303.1.1.2 Class 3 Liquid and Solid Oxidizers
5705.3.5 Flammable and Combustible Liquids, Quantity Limits for Use
not exceed that necessary for demonstration, treatment, laboratory work, maintenance purposes and operation of equipment and shall not exceed quantities set ...
California Fire Code 2019 > 57 Flammable and Combustible Liquids > 5705 Dispensing, Use, Mixing and Handling > 5705.3 Use, Dispensing and Mixing Inside of Buildings > 5705.3.5 Quantity Limits for Use