1910.110(e)(5)(iv) Liquid-Level Gaging Devices
JUMP TO FULL CODE CHAPTER
Variable liquid-level gages which require the venting of fuel to the atmosphere shall not be used on fuel containers of industrial trucks (including lift trucks).
On portable containers that may be filled in the vertical and/or horizontal position, the fixed liquid-level gage must indicate maximum permitted filling level for both vertical and horizontal filling with the container oriented to place the safety relief valve in communication with the vapor space.
In the case of containers used solely in farm tractor service, and charged at a point at least 50 feet from any important building, the fixed liquid-level gaging device may be so constructed that the outward flow of container content exceeds that passed by a No. 54 drill size opening, but in no case shall the flow exceed that passed by a No. 31 drill-size opening. An excess flow valve is not required. Fittings equipped with such restricted drill size opening and container on which they are used shall be marked to indicate the size of the opening.
All valves and connections on containers shall be adequately protected to prevent damage due to accidental contact with stationary objects or from loose objects thrown up from the road, and all valves shall be safeguarded against damage due to collision, overturning or other accident. For farm tractors where parts of the vehicle provide such protection to valves and fittings, the foregoing requirements shall be considered fulfilled. However, on removable type containers the protection for the fittings shall be permanently attached to the container.
When removable fuel containers are used, means shall be provided in the fuel system to minimize the escape of fuel when the containers are exchanged. This may be accomplished by either of the following methods:
Using an approved automatic quick-closing coupling (a type closing in both directions when uncoupled) in the fuel line, or
Closing the valve at the fuel container and allowing the engine to run until the fuel in the line is consumed.
Related Code Sections
1910.110(b)(19) Hazardous Materials, Liquid-Level Gaging Device
All variable gaging devices shall be arranged so that the maximum liquid level for butane, for a 50 - 50 mixture of butane and propane ...
OSHA 1910 General Industry > H Hazardous Materials > 1910.110 Storage and Handling of Liquefied Petroleum Gases > 1910.110(b) Basic Rules > 1910.110(b)(19) Liquid-Level Gaging Device
1910.111(b)(14) Hazardous Materials, Liquid-Level Gaging Device
Each container except those filled by weight shall be equipped with an approved liquid-level gaging device. A thermometer well shall be provided ...
OSHA 1910 General Industry > H Hazardous Materials > 1910.111 Storage and Handling of Anhydrous Ammonia > 1910.111(b) Basic Rules > 1910.111(b)(14) Liquid-Level Gaging Device
1910.111(b)(14)(iv) Hazardous Materials,
Gaging devices shall have a design pressure equal to or greater than the design pressure of the container on which they are installed ...
OSHA 1910 General Industry > H Hazardous Materials > 1910.111 Storage and Handling of Anhydrous Ammonia > 1910.111(b) Basic Rules > 1910.111(b)(14) Liquid-Level Gaging Device > 1910.111(b)(14)(iv)
1910.111(b)(14)(vi) Hazardous Materials,
Gage glasses of the columnar type shall be restricted to stationary storage installations. They shall be equipped with shutoff valves having metallic ...
OSHA 1910 General Industry > H Hazardous Materials > 1910.111 Storage and Handling of Anhydrous Ammonia > 1910.111(b) Basic Rules > 1910.111(b)(14) Liquid-Level Gaging Device > 1910.111(b)(14)(vi)
1910.111(b)(14)(iii) Hazardous Materials,
Gaging devices that require bleeding of the product to the atmosphere such as the rotary tube, fixed tube, and slip tube devices shall be designed so ...
OSHA 1910 General Industry > H Hazardous Materials > 1910.111 Storage and Handling of Anhydrous Ammonia > 1910.111(b) Basic Rules > 1910.111(b)(14) Liquid-Level Gaging Device > 1910.111(b)(14)(iii)