5803.1.6 Liquefied Flammable Gases and Flammable Gases in Solution
JUMP TO FULL CODE CHAPTER
Containers of liquefied flammable gases and flammable gases in solution shall be positioned in the upright position or positioned so that the pressure relief valve is in direct contact with the vapor space of the container.
Exceptions:
- Containers of flammable gases in solution with a capacity of 1.3 gallons (5 L) or less.
- Containers of flammable liquefied gases, with a capacity not exceeding 1.3 gallons (5 L), designed to preclude the discharge of liquid from safety relief devices.
Related Code Sections
5803.1.6 Flammable Gases and Flammable Cryogenic Fluids, Liquefied Flammable Gases and Flammable Gases in Solution
Containers of liquefied flammable gases and flammable gases in solution shall be positioned in the upright position or positioned so ...
2020 Minnesota State Fire Code > 58 Flammable Gases and Flammable Cryogenic Fluids > 5803 General Requirements > 5803.1 Quantities Not Exceeding the Maximum Allowable Quantity Per Control Area > 5803.1.6 Liquefied Flammable Gases and Flammable Gases in Solution
5803.1.6 Flammable Gases and Flammable Cryogenic Fluids, Liquefied Flammable Gases and Flammable Gases in Solution
Containers of liquefied flammable gases and flammable gases in solution shall be positioned in the upright position or positioned so ...
Minnesota Fire Code 2015 > 58 Flammable Gases and Flammable Cryogenic Fluids > 5803 General Requirements > 5803.1 Quantities Not Exceeding the Maximum Allowable Quantity Per Control Area > 5803.1.6 Liquefied Flammable Gases and Flammable Gases in Solution
Section 3306 Fire Safety During Construction and Demolition, Flammable Gases
The storage, use and handling of flammable gases shall comply with Chapter 58 ...
2020 Minnesota State Fire Code > 33 Fire Safety During Construction and Demolition > 3306 Flammable Gases
Section 3306 Fire Safety During Construction and Demolition, Flammable Gases
The storage, use and handling of flammable gases shall comply with Chapter 58 ...
Section 5802 Flammable Gases and Flammable Cryogenic Fluids, Definitions
The following terms are defined in Chapter 2: FLAMMABLE GAS. FLAMMABLE LIQUEFIED GAS. METAL HYDRIDE. METAL HYDRIDE STORAGE SYSTEM ...