P2709.2 Lining Required
JUMP TO FULL CODE CHAPTER
The adjoining walls and floor framing enclosing on-site built-up shower receptors shall be lined with one of the following materials:
- Sheet lead.
- Sheet copper.
- Plastic liner material that complies with ASTM D4068 or ASTM D4551.
- Hot mopping in accordance with Section P2709.2.3.
- Sheet-applied load-bearing, bonded waterproof membranes that comply with ANSI A118.10.
The lining material shall extend not less than 2 inches (51 mm) beyond or around the rough jambs and not less than 2 inches (51 mm) above finished thresholds. Sheet-applied load bearing, bonded waterproof membranes shall be applied in accordance with the manufacturer's instructions.
Plasticized polyvinyl chloride (PVC) sheet shall meet the requirements of ASTM D4551. Sheets shall be joined by solvent welding in accordance with the manufacturer's instructions.
Nonplasticized chlorinated polyethylene sheet shall meet the requirements of ASTM D4068. The liner shall be joined in accordance with the manufacturer's instructions.
Shower receptors lined by hot mopping shall be built-up with not less than three layers of standard grade Type 15 asphalt-impregnated roofing felt. The bottom layer shall be fitted to the formed subbase and each succeeding layer thoroughly hot-mopped to that below. Corners shall be carefully fitted and shall be made strong and water tight by folding or lapping, and each corner shall be reinforced with suitable webbing hot-mopped in place. Folds, laps and reinforcing webbing shall extend not less than 4 inches (102 mm) in all directions from the corner and webbing shall be of approved type and mesh, producing a tensile strength of not less than 50 pounds per inch (893 kg/m) in either direction.
Liquid-type, trowel-applied, load-bearing, bonded waterproof materials shall meet the requirements of ANSI A118.10 and shall be applied in accordance with the manufacturer's instructions.
Related Code Sections
P2709.2 Plumbing Fixtures, Lining Required
The adjoining walls and floor framing enclosing on-site built-up shower receptors shall be lined with one of the following materials: Sheet lead ...
Residential Code 2018 of Kansas > 27 Plumbing Fixtures > P2709 Shower Receptors > P2709.2 Lining Required
8.14.9 Installation Requirements,
Pilot line detectors located in open-sided buildings shall follow the indoor spacing rules ...
Standard for the Installation of Sprinkler Systems 2016 of Kansas > 8 Installation Requirements > 8.14 Pilot Line Detectors > 8.14.9
8.14.10.1 Installation Requirements,
Pipe supplying pilot line detectors shall not be required to meet the requirements of 9.3.5 ...
Standard for the Installation of Sprinkler Systems 2016 of Kansas > 8 Installation Requirements > 8.14 Pilot Line Detectors > 8.14.10 > 8.14.10.1
8.14.1 Installation Requirements,
Pilot line detectors and related components including pipe and fittings shall be corrosion resistant when installed in areas exposed to weather ...
Standard for the Installation of Sprinkler Systems 2016 of Kansas > 8 Installation Requirements > 8.14 Pilot Line Detectors > 8.14.1
8.14.10 Installation Requirements,
Pipe supplying pilot line detectors shall be permitted to be supported from the same points of hanger attachment as the piping system it serves ...
Standard for the Installation of Sprinkler Systems 2016 of Kansas > 8 Installation Requirements > 8.14 Pilot Line Detectors > 8.14.10