408.7 Lining for Showers and Receptors
JUMP TO FULL CODE CHAPTER
Shower receptors
built on-site shall be watertight and shall be constructed
from approved-type dense, nonabsorbent, and noncorrosive
materials. Each such receptor shall be adequately reinforced,
shall be provided with an approved flanged floor drain
designed to make a watertight joint in the floor, and shall
have smooth, impervious, and durable surfaces.
Shower receptors shall have the subfloor and rough side of walls to a height of not less than 3 inches (76 mm) above the top of the finished dam or threshold shall be first lined with sheet plastic, lead, or copper, or shall be lined with other durable and watertight materials. Showers that are provided with a built in place, permanent seat or seating area that is located within the shower enclosure, shall be first lined with sheet plastic, lead, copper, or shall be lined with other durable and watertight materials that extend not less than 3 inches (76 mm) above horizontal surfaces of the seat or the seating area.
Lining materials shall be pitched 1/4 inch per foot (20.8 mm/m) to weep holes in the subdrain of a smooth and solidly formed subbase. Such lining materials shall extend upward on the rough jambs of the shower opening to a point not less than 3 inches (76 mm) above the horizontal surfaces of the seat or the seating area, the top of the finished dam or threshold and shall extend outward over the top of the permanent seat, permanent seating area, or rough threshold and be turned over and fastened on the outside face of both the permanent seat, permanent seating area, or rough threshold and the jambs.
Nonmetallic shower subpans or linings shall be permitted to be built up on the job site of not less than three layers of standard grade 15 pound (6.8 kg) asphalt-impregnated roofing felt. The bottom layer shall be fitted to the formed subbase and each succeeding layer thoroughly hot-mopped to that below. Corners shall be carefully fitted and shall be made strong and watertight by folding or lapping, and each corner shall be reinforced with suitable webbing hot-mopped in place.
Folds, laps, and reinforcing webbing shall extend not less than 4 inches (102 mm) in all directions from the corner, and webbing shall be of approved type and mesh, producing a tensile strength of not less than 50 pounds per square foot (lb/ft2) (244 kg/m2) in either direction. Nonmetallic shower subpans or linings shall be permitted to consist of multilayers of other approved equivalent materials suitably reinforced and carefully fitted in place on the job site as elsewhere required in this section.
Linings shall be properly recessed and fastened to approved backing so as not to occupy the space required for the wall covering, and shall not be nailed or perforated at a point that is less than 1 inch (25.4 mm) above the finished dam or threshold. An approved-type subdrain shall be installed with a shower subpan or lining. Each such subdrain shall be of the type that sets flush with the subbase and shall be equipped with a clamping ring or other device to make a tight connection between the lining and the drain. The subdrain shall have weep holes into the waste line. The weep holes located in the subdrain clamping ring shall be protected from clogging.
Shower receptors shall have the subfloor and rough side of walls to a height of not less than 3 inches (76 mm) above the top of the finished dam or threshold shall be first lined with sheet plastic, lead, or copper, or shall be lined with other durable and watertight materials. Showers that are provided with a built in place, permanent seat or seating area that is located within the shower enclosure, shall be first lined with sheet plastic, lead, copper, or shall be lined with other durable and watertight materials that extend not less than 3 inches (76 mm) above horizontal surfaces of the seat or the seating area.
Lining materials shall be pitched 1/4 inch per foot (20.8 mm/m) to weep holes in the subdrain of a smooth and solidly formed subbase. Such lining materials shall extend upward on the rough jambs of the shower opening to a point not less than 3 inches (76 mm) above the horizontal surfaces of the seat or the seating area, the top of the finished dam or threshold and shall extend outward over the top of the permanent seat, permanent seating area, or rough threshold and be turned over and fastened on the outside face of both the permanent seat, permanent seating area, or rough threshold and the jambs.
Nonmetallic shower subpans or linings shall be permitted to be built up on the job site of not less than three layers of standard grade 15 pound (6.8 kg) asphalt-impregnated roofing felt. The bottom layer shall be fitted to the formed subbase and each succeeding layer thoroughly hot-mopped to that below. Corners shall be carefully fitted and shall be made strong and watertight by folding or lapping, and each corner shall be reinforced with suitable webbing hot-mopped in place.
Folds, laps, and reinforcing webbing shall extend not less than 4 inches (102 mm) in all directions from the corner, and webbing shall be of approved type and mesh, producing a tensile strength of not less than 50 pounds per square foot (lb/ft2) (244 kg/m2) in either direction. Nonmetallic shower subpans or linings shall be permitted to consist of multilayers of other approved equivalent materials suitably reinforced and carefully fitted in place on the job site as elsewhere required in this section.
Linings shall be properly recessed and fastened to approved backing so as not to occupy the space required for the wall covering, and shall not be nailed or perforated at a point that is less than 1 inch (25.4 mm) above the finished dam or threshold. An approved-type subdrain shall be installed with a shower subpan or lining. Each such subdrain shall be of the type that sets flush with the subbase and shall be equipped with a clamping ring or other device to make a tight connection between the lining and the drain. The subdrain shall have weep holes into the waste line. The weep holes located in the subdrain clamping ring shall be protected from clogging.
Plasticized polyvinyl chloride
(PVC) sheets shall comply with ASTM D4551. Sheets
shall be joined by solvent cementing in accordance with
the manufacturer's installation instructions.
Nonplasticized
chlorinated polyethylene sheets shall comply
with ASTM D4068. The liner shall be joined in accordance
with the manufacturer's installation instructions.
Sheet lead shall weigh not less than
4 lb/ft2 (19 kg/m2) and shall be coated with an asphalt
paint or other approved coating. The lead sheet shall be
insulated from conducting substances, other than the connecting
drain, by 15 pound (6.8 kg) asphalt felt or an
equivalent. Sheet lead shall be joined by burning.
Sheet copper shall comply with
ASTM B152 and shall weigh not less than 12 ounces per
square foot (oz/ft2) (3.7 kg/m2) or No. 24 B & S Gauge
(0.02 inches) (0.51 mm). The copper sheet shall be insulated
from conducting substances, other than the connecting
drain, by 15 pound (6.8 kg) asphalt felt or an
equivalent. Sheet copper shall be joined by brazing or
soldering.
Related Code Sections
408.7 Plumbing Fixtures and Fixture Fittings, Lining for Showers and Receptors
Shower receptors
built on-site shall be watertight and shall be constructed
from approved-type dense, nonabsorbent, and noncorrosive
materials. Each ...
California Plumbing Code 2016 > 4 Plumbing Fixtures and Fixture Fittings > 408.0 Showers > 408.7 Lining for Showers and Receptors
408.7 Plumbing Fixtures and Fixture Fittings, Lining for Showers and Receptors
Shower
receptors built on-site shall be watertight and shall be constructed
from approved-type dense, nonabsorbent, and noncorrosive
materials. Each ...
California Plumbing Code 2019 > 4 Plumbing Fixtures and Fixture Fittings > 408.0 Showers > 408.7 Lining for Showers and Receptors
408.7.2 Plumbing Fixtures and Fixture Fittings, Chlorinated Polyethylene (CPE) Sheets
Nonplasticized chlorinated polyethylene sheets shall conform to ASTM D4068. The liner shall be joined in
accordance with the manufacturer's ...
California Plumbing Code 2019 > 4 Plumbing Fixtures and Fixture Fittings > 408.0 Showers > 408.7 Lining for Showers and Receptors > 408.7.2 Chlorinated Polyethylene (CPE) Sheets
408.7.3 Plumbing Fixtures and Fixture Fittings, Sheet Lead
Sheet lead shall weigh not less than
4 lb/ft 2 (19 kg/m 2 ) and shall be coated with an asphalt
paint or other approved coating. The lead sheet shall ...
California Plumbing Code 2016 > 4 Plumbing Fixtures and Fixture Fittings > 408.0 Showers > 408.7 Lining for Showers and Receptors > 408.7.3 Sheet Lead
408.7.3 Plumbing Fixtures and Fixture Fittings, Sheet Lead
Sheet lead shall weigh not less
than 4 lb/ft 2 (19.5 kg/m 2 ) and shall be coated with an
asphalt paint or other approved coating. The lead sheet ...
California Plumbing Code 2019 > 4 Plumbing Fixtures and Fixture Fittings > 408.0 Showers > 408.7 Lining for Showers and Receptors > 408.7.3 Sheet Lead