1910.140(e)(1)(iv) Lineman's Body Belt and Pole Strap Systems
JUMP TO FULL CODE CHAPTER
Lineman's body belt and pole strap systems must meet the following tests:
A dielectric test of 819.7 volts, AC, per centimeter (25,000 volts per foot) for 3 minutes without visible deterioration;
A leakage test of 98.4 volts, AC, per centimeter (3,000 volts per foot) with a leakage current of no more than 1 mA; and
A flammability test in accordance with Table I-7 of this section.
Test Method | Criteria for Passing Test |
1.Vertically suspend a 19.7-inch (500-mm) length of strapping supporting a 220.5-lb (100-kg) weight; | Any flames on the positioning strap must self-extinguish. |
2. Use a butane or propane burner with a 3-inch (76-mm) flame; | The positioning strap must continue to support the 220.5-lb (100kg) mass. |
3. Direct the flame to an edge of the strapping at a distance of 1 inch (25-mm); | |
4. Remove the flame after 5 seconds; and | |
5. Wait for any flames on the positioning strap to stop burning. |
Related Code Sections
1910.140(e)(1)(iv) Personal Protective Equipment, Lineman's Body Belt and Pole Strap Systems
Lineman's body belt and pole strap systems must meet the following tests ...
OSHA 1910 General Industry > I Personal Protective Equipment > 1910.140 Personal Fall Protection Systems > 1910.140(e) Positioning Systems > 1910.140(e)(1) System Performance Requirements > 1910.140(e)(1)(iv) Lineman's Body Belt and Pole Strap Systems
1910.140 Personal Protective Equipment, Personal Fall Protection Systems
). Lineman's body belt and pole strap systems must meet ...
OSHA 1910 General Industry > I Personal Protective Equipment > 1910.140 Personal Fall Protection Systems
Appendix F Special Industries, Work-Positioning Equipment Inspection Guidelines
Appendix F to ยง 1910.269-Work-Positioning Equipment Inspection Guidelines
Body Belts
Inspect body belts to ensure that:
The ...
OSHA 1910 General Industry > R Special Industries > 1910.269 Electric Power Generation, Transmission, and Distribution > F Work-Positioning Equipment Inspection Guidelines
1910.268(n)(8) Special Industries, Other Elevated Locations
Safety straps and body belts shall be worn when working at elevated positions on poles, towers or similar structures, which do not have adequately ...
OSHA 1910 General Industry > R Special Industries > 1910.268 Telecommunications > 1910.268(n) Overhead Lines > 1910.268(n)(8) Other Elevated Locations
1910.268(n)(7) Special Industries, Outside Work Platforms
Unless adequate railings are provided, safety straps and body belts shall be used while working on elevated work platforms such as aerial splicing ...
OSHA 1910 General Industry > R Special Industries > 1910.268 Telecommunications > 1910.268(n) Overhead Lines > 1910.268(n)(7) Outside Work Platforms