R602.10.6.5.3 Limited Veneer Exceeding First-Story Height
JUMP TO FULL CODE CHAPTER
Where detached one- or two-family dwellings in Seismic Design Categories D0, D1 and D2 have exterior veneer installed in accordance with Section R703.8 and where brick veneer installed above the first-story height meets the following limitations, bracing in accordance with Method WSP or CS-WSP shall be permitted provided that the total length of braced wall panels specified by Table R602.10.3(3) is multiplied by 1.2 for each first- and second-story braced wall line.
- The dwelling does not extend more than two stories above grade plane.
- The veneer does not exceed 5 inches (127 mm) in thickness.
- The height of veneer on gable-end walls does not extend more than 8 feet (2438 mm) above the bearing wall top plate elevation.
- Where veneer is installed on multiple walls above the first story, the total area of the veneer on the second-story exterior walls shall not exceed 25 percent of the occupied second floor area.
- Where the veneer is installed on one entire second-story exterior wall, including walls on bay windows and similar appurtenances, brick veneer shall not be installed on any of the other walls on that floor.
Related Code Sections
R602.10.6.5.3 Wall Construction, Limited Veneer Exceeding First-Story Height
with Section R703.8 and where brick veneer installed above the first-story height meets the following limitations, bracing in accordance with Method WSP or CS ...
Residential Code 2021 of Colorado > 6 Wall Construction > R602 Wood Wall Framing > R602.10 Wall Bracing > R602.10.6 Construction of Methods ABW, PFH, PFG, CS-PF and BV-WSP > R602.10.6.5 Wall Bracing for Dwellings With Stone and Masonry Veneer in Seismic Design Categories D0, D1 and D2 > R602.10.6.5.3 Limited Veneer Exceeding First-Story Height
2308.6.10 Wood, Limitations of Concrete or Masonry Veneer
and masonry veneer is permitted to be used in the first story above grade plane or the first two stories above grade plane where the lowest story ...
Building Code of the Department of Personnel & Administration/Office of the State Architect (DPA/OSA) > 23 Wood > 2308 Conventional Light-Frame Construction > 2308.6 Wall Bracing > 2308.6.10 Limitations of Concrete or Masonry Veneer
2308.6.10 Wood, Limitations of Concrete or Masonry Veneer
Stone and masonry veneer is permitted to be used in the first story above grade plane or the first two stories above grade plane where ...
Building Code of the Department of Personnel & Administration/Office of the State Architect (DPA/OSA) > 23 Wood > 2308 Conventional Light-Frame Construction > 2308.6 Wall Bracing > 2308.6.10 Limitations of Concrete or Masonry Veneer
2308.6.10 Wood, Limitations of Concrete or Masonry Veneer
Stone and masonry veneer is permitted to be used in the first story above grade plane or the first two stories above grade plane where ...
Building Code 2021 of Colorado > 23 Wood > 2308 Conventional Light-Frame Construction > 2308.6 Wall Bracing > 2308.6.10 Limitations of Concrete or Masonry Veneer
R301.3 Building Planning, Story Height
be permitted to exceed these limits as permitted by Chapter 6, provided that the story heights of this section are not exceeded. An engineered ...
Residential Code 2021 of Colorado > 3 Building Planning > R301 Design Criteria > R301.3 Story Height