• Codes
  • Features

    Features Overview

    Go to features
    Reference

    Reference.

    A reliable and up-to-date source of codes.
    Research

    Research.

    Rapidly and efficiently calculate project parameters.
    Collaboration

    Collaboration.

    Get everyone on the same page and streamline code research.
    Workflows
    Architects General Contractor Building Official & Plans Examiner Inspectors Owner Subcontractors Code Consultants
  • Pricing
  • Login
  • Sign Up
Sign Up
Login
  • Code Library
  • Features
  • Pricing
  • About
  • Careers
  • Help
  • Contact
  • Terms
  • Privacy
Sign Up
Upgrade to Premium
Code calculators: Code Calculators automatically generates a detailed list of requirements.
REFERENCE
Amendment Styling
Industry-leading search
Suggested code sections
Code diagrams
RESEARCH
Code calculators
Filter by topic
Code compare
Code sheet exports
COLLABORATION
Team projects
Bookmarks
Comments
START 2 WEEK FREE TRIAL
Have an account? Sign in
// CODE SNIPPET

C408.3 Lighting System Functional Testing

2017 FBC - Energy Conservation, 6th edition > 4 [CE] Commercial Energy Efficiency > C408 System Commissioning > C408.3 Lighting System Functional Testing
JUMP TO FULL CODE CHAPTER
Controls for automatic lighting systems shall comply with this section.

C408.3.1 Functional Testing

Prior to passing final inspection, the registered design professional shall provide evidence that the lighting control systems have been tested to ensure that control hardware and software are calibrated, adjusted, programmed and in proper working condition in accordance with the construction documents and manufacturer's instructions. Functional testing shall be in accordance with Sections C408.3.1.1 and C408.3.1.2 for the applicable control type.

C408.3.1.1 Occupant Sensor Controls

Where occupant sensor controls are provided, the following procedures shall be performed:

  1. Certify that the occupant sensor has been located and aimed in accordance with manufacturer recommendations.
  2. For projects with seven or fewer occupant sensors, each sensor shall be tested.
  3. For projects with more than seven occupant sensors, testing shall be done for each unique combination of sensor type and space geometry. Where multiples of each unique combination of sensor type and space geometry are provided, not less than 10 percent, but in no case less than one, of each combination shall be tested unless the code official or design professional requires a higher percentage to be tested. Where 30 percent or more of the tested controls fail, all remaining identical combinations shall be tested.

    For occupant sensor controls to be tested, verify the following:

    1. 3.1. Where occupant sensor controls include status indicators, verify correct operation.
    2. 3.2. The controlled lights turn off or down to the permitted level within the required time.
    3. 3.3. For auto-on occupant sensor controls, the lights turn on to the permitted level when an occupant enters the space.
    4. 3.4. For manual-on occupant sensor controls, the lights turn on only when manually activated.
    5. 3.5. The lights are not incorrectly turned on by movement in adjacent areas or by HVAC operation.

C408.3.1.2 Time-Switch Controls

Where time-switch controls are provided, the following procedures shall be performed:

  1. Confirm that the time-switch control is programmed with accurate weekday, weekend and holiday schedules.
  2. Provide documentation to the owner of time-switch controls programming including weekday, weekend, holiday schedules, and set-up and preference program settings.
  3. Verify the correct time and date in the time switch.
  4. Verify that any battery back-up is installed and energized.
  5. Verify that the override time limit is set to not more than 2 hours.
  6. Simulate occupied condition. Verify and document the following:

    1. 6.1. All lights can be turned on and off by their respective area control switch.
    2. 6.2. The switch only operates lighting in the enclosed space in which the switch is located.
  7. Simulate unoccupied condition. Verify and document the following:

    1. 7.1. Nonexempt lighting turns off.
    2. 7.2. Manual override switch allows only the lights in the enclosed space where the override switch is located to turn on or remain on until the next scheduled shutoff occurs.
  8. Additional testing as specified by the registered design professional.

C408.3.1.3 Daylight Responsive Controls

Where daylight responsive controls are provided, the following shall be verified:

  1. Control devices have been properly located, field calibrated and set for accurate setpoints and threshold light levels.
  2. Daylight controlled lighting loads adjust to light level set points in response to available daylight.
  3. The locations of calibration adjustment equipment are readily accessible only to authorized personnel.

C408.3.2 Documentation Requirements

The construction documents shall specify that documents certifying that the installed lighting controls meet documented performance criteria of Section C405 are to be provided to the building owner within 90 days from the date of receipt of the certificate of occupancy.

Related Code Sections


C408.3 [CE] Commercial Energy Efficiency, Lighting System Functional Testing
Controls for automatic lighting systems shall comply with this section ...
2017 FBC - Energy Conservation, 6th edition > 4 [CE] Commercial Energy Efficiency > C408 System Commissioning > C408.3 Lighting System Functional Testing
C408.3 [CE] Commercial Energy Efficiency, Lighting System Functional Testing
of the project shall be responsible for the functional testing and shall provide documentation to the code official certifying that the installed lighting ...
2014 FBC - Energy Conservation, 5th edition > 4 [CE] Commercial Energy Efficiency > C408 System Commissioning > C408.3 Lighting System Functional Testing
C408.3.1.1 [CE] Commercial Energy Efficiency, Occupant Sensor Controls
and aimed in accordance with manufacturer recommendations. For projects with seven or fewer occupant sensors , each sensor shall be tested. For ...
2017 FBC - Energy Conservation, 6th edition > 4 [CE] Commercial Energy Efficiency > C408 System Commissioning > C408.3 Lighting System Functional Testing > C408.3.1 Functional Testing > C408.3.1.1 Occupant Sensor Controls
C408.3.1 [CE] Commercial Energy Efficiency, Functional Testing
Prior to passing final inspection, the registered design professional shall provide evidence that the lighting control systems have been tested ...
2020 FBC - Energy Conservation, 7th edition > 4 [CE] Commercial Energy Efficiency > C408 Maintenance Information and System Commissioning > C408.3 Lighting Controls Functional Testing > C408.3.1 Functional Testing
C408.3.2 [CE] Commercial Energy Efficiency, Documentation Requirements
A report of test results shall be provided and include the following: Results of functional performance tests ...
2020 FBC - Energy Conservation, 7th edition > 4 [CE] Commercial Energy Efficiency > C408 Maintenance Information and System Commissioning > C408.3 Lighting Controls Functional Testing > C408.3.2 Documentation Requirements
Help Contact Us Privacy Terms
Shared projects
Shared projects
Projects provide a dedicated space to collaborate on code research.
Code diagrams
Code diagrams
Unpack the code through illustrations and descriptions.
Search
Search
Don't miss relevant code. Quickly locate sections across your jurisdiction.
Code Compare
Code Compare
Highlight differences between any two building codes.
Code sheet exports
Code sheet exports
Generate a code sheet that integrates with your drawing set.
Code Calculators
Code Calculators
Code calculators automatically generate a detailed list of requirements.
UpCodes Premium
Leverage the most sophisticated code compliance platform.
TRY FREE FOR TWO WEEKS VISIT PRICING
UpCodes Premium
Leverage the full code compliance platform.
START 2 WEEK FREE TRIAL LEARN MORE