E3903.1 General
Lighting outlets shall be provided in accordance with Sections E3903.2 through E3903.4. [210.70(A)]
E3903.2 Habitable Rooms
At least one lighting outlet controlled by a listed wall-mounted control device shall be installed in every habitable room, kitchen and bathroom. The wall-mounted control device shall be located near an entrance to the room on a wall. [210.70(A)(1)]

Exceptions:
  1. In other than kitchens and bathrooms, one or more receptacles controlled by a listed wall-mounted control device shall be considered equivalent to the required lighting outlet. [210.70(A)(1) Exception No. 1]
  2. Lighting outlets shall be permitted to be controlled by occupancy sensors that are in addition to listed walll-mounted control devices or that are located at a customary wall switch location and equipped with a manual override that will allow the sensor to function as a wall switch. [210.70(A)(1) Exception No. 2]
E3903.3 Additional Locations
At least one lighting outlet controlled by a listed wall-mounted control device shall be installed in hallways, stairways, attached garages, and detached garages with electric power. At least one lighting outlet controlled by a listed wall-mounted control device shall be installed to provide illumination on the exterior side of each outdoor egress door having grade level access, including outdoor egress doors for attached garages and detached garages with electric power. A vehicle door in a garage shall not be considered as an outdoor egress door.
E3903.3.1 Stairway Lighting Outlet Control
Where one or more lighting outlets are installed for interior stairways, there shall be a listed wall-mounted control device at each floor level and landing level that includes an entryway to control the lighting outlets where the stairway between floor levels has six or more risers. Lighting outlets installed to meet this requirement shall not be controlled by the use of listed wall-mounted control devices except where the devices provide the full range of dimming control at each switch location. [210.70(A)(2)]
Exception: In hallways, stairways, and at outdoor egress doors, remote, central, or automatic control of lighting shall be permitted. [210.70(A)(2) Exception]
E3903.4 Storage or Equipment Spaces
In attics, under-floor spaces, utility rooms and basements, at least one lighting outlet shall be installed where these spaces are used for storage or contain equipment requiring servicing. Such lighting outlet shall be controlled by a wall switch or listed wall-mounted control device. A point of control shall be provided at each entry that permits access to the attic or underfloor space, utility room, or basement. Where a lighting outlet is installed for equipment requiring service, the lighting outlet shall be installed at or near the equipment requiring servicing. [210.70(C)]

Related Code Sections

Section E3903 Power and Lighting Distribution, Lighting Outlets
Lighting outlets shall be provided in accordance with Sections E3903.2 through E3903.4. [210.70(A ...
806.4.5 Alterations—Level 2, Minimum Lighting Outlets
Not fewer than one lighting outlet shall be provided in every bathroom, hallway, stairway, attached garage and detached garage with electric power ...
807.3.5 Alterations—Level 2, Minimum Lighting Outlets
Not fewer than one lighting outlet shall be provided in every bathroom, hallway, stairway, attached garage, and detached garage with electric power ...
808.3.5 Alterations - Level 2, Minimum Lighting Outlets
At least one lighting outlet shall be provided in every bathroom, hallway, stairway, attached garage, and detached garage with electric power ...