1910.306(j)(2) Lighting Fixtures, Lighting Outlets, and Ceiling Suspended (Paddle) Fans
JUMP TO FULL CODE CHAPTER
In outdoor pool areas, lighting fixtures, lighting outlets, and ceiling-suspended (paddle) fans may not be installed over the pool or over the area extending 1.52 m (5 ft) horizontally from the inside walls of a pool unless no part of the lighting fixture of a ceiling-suspended (paddle) fan is less than 3.66 m (12 ft) above the maximum water level. However, a lighting fixture or lighting outlet that was installed before April 16, 1981, may be located less than 1.52 m (5 ft) measured horizontally from the inside walls of a pool if it is at least 1.52 m (5 ft) above the surface of the maximum water level and is rigidly attached to the existing structure. It shall also be protected by a ground-fault circuit interrupter installed in the branch circuit supplying the fixture.
Lighting fixtures and lighting outlets installed in the area extending between 1.52 m (5 ft) and 3.05 m (10 ft) horizontally from the inside walls of a pool shall be protected by a ground-fault circuit interrupter unless installed 1.52 m (5 ft) above the maximum water level and rigidly attached to the structure adjacent to or enclosing the pool.
Related Code Sections
1910.306(j)(2) Electrical, Lighting Fixtures, Lighting Outlets, and Ceiling Suspended (Paddle) Fans
In outdoor pool areas, lighting fixtures, lighting outlets, and ceiling-suspended (paddle) fans may not be installed over the pool or over the area ...
OSHA 1910 General Industry > S Electrical > 1910.306 Specific Purpose Equipment and Installations > 1910.306(j) Swimming Pools, Fountains, and Similar Installations > 1910.306(j)(2) Lighting Fixtures, Lighting Outlets, and Ceiling Suspended (Paddle) Fans
1910.142(g) General Environmental Controls, Lighting
Where electric service is available, each habitable room in a camp shall be provided with at least one ceiling-type light fixture and at least one ...
OSHA 1910 General Industry > J General Environmental Controls > 1910.142 Temporary Labor Camps > 1910.142(g) Lighting
1910.110(d)(16) Hazardous Materials, Lighting
Electrical equipment and installations shall conform to paragraphs (b) (17) and (18) of this section ...
OSHA 1910 General Industry > H Hazardous Materials > 1910.110 Storage and Handling of Liquefied Petroleum Gases > 1910.110(d) > 1910.110(d)(16) Lighting
1910.179(c)(4) Materials Handling and Storage, Lighting
Light in the cab shall be sufficient to enable the operator to see clearly enough to perform his work ...
OSHA 1910 General Industry > N Materials Handling and Storage > 1910.179 Overhead and Gantry Cranes > 1910.179(c) Cabs > 1910.179(c)(4) Lighting
1910.262(c)(6) Special Industries, Lighting
Lighting shall conform to American National Standard A11.1—1965, which is incorporated by reference as specified in §1910.6 ...
OSHA 1910 General Industry > R Special Industries > 1910.262 Textiles > 1910.262(c) General Safety Requirements > 1910.262(c)(6) Lighting