611.9.2.6 Lighting Documentation
JUMP TO FULL CODE CHAPTER
The following documentation for lights, systems and control devices shall be provided to the building owner:
- Settings determined during commissioning activities outlined in Section 611.9.2.
- A narrative describing the intent and functionality of all controls including any capability for users to override a schedule or master command.
- Specification sheets for all lighting equipment and controls.
- Operation manuals for each lighting control device. Required maintenance and maintenance schedules shall be clearly identified. Documentation and instructions necessary for building maintenance personnel to maintain and recalibrate lighting systems and controls.
- An annual inspection schedule for lighting controls.
- Troubleshooting information for dimming systems and the remediation of switching issues such as false-ons and false-offs.
Related Code Sections
611.9.2.6 Energy Conservation, Efficiency and Co2e Emission Reduction, Lighting Documentation
The following documentation for lights, systems and control devices shall be provided to the building owner: Settings determined during ...
Green Construction Code 2015 > 6 Energy Conservation, Efficiency and Co2e Emission Reduction > 611 Energy Systems Commissioning and Completion > 611.9 Lighting and Electrical Systems Commissioning > 611.9.2 Lighting Controls Commissioning > 611.9.2.6 Lighting Documentation
611.3.1 ENERGY CONSERVATION, EFFICIENCY AND CO2e EMISSION REDUCTION, Preconstruction Documentation, Lighting
Construction and owner education documents shall include floor plans, diagrams and notations of sufficient clarity describing the types of, location ...
Green Construction Code 2012 > 6 ENERGY CONSERVATION, EFFICIENCY AND CO2e EMISSION REDUCTION > 611 Energy Systems Commissioning and Completion > 611.3 Lighting and Electrical Systems Commissioning and Completion Requirements > 611.3.1 Preconstruction Documentation, Lighting
C408.3.2 [CE] Commercial Energy Efficiency, Documentation Requirements
The construction documents shall specify that documents certifying that the installed lighting controls meet documented performance criteria ...
Energy Conservation Code 2015 > 4 [CE] Commercial Energy Efficiency > C408 System Commissioning > C408.3 Lighting System Functional Testing > C408.3.2 Documentation Requirements
C408.3.2.2 [CE] Commercial Energy Efficiency, Manuals
for each piece of lighting equipment and lighting controls. Operation and maintenance manuals for each piece of lighting equipment. Required routine ...
Energy Conservation Code 2018 > 4 [CE] Commercial Energy Efficiency > C408 Maintenance Information and System Commissioning > C408.3 Functional Testing of Lighting Controls > C408.3.2 Documentation Requirements > C408.3.2.2 Manuals
C408.3.1.2 [CE] Commercial Energy Efficiency, Time-Switch Controls
in the enclosed space in which the switch is located. Simulate unoccupied condition. Verify and document the following: 7.1. Nonexempt lighting turns off ...
Energy Conservation Code 2015 > 4 [CE] Commercial Energy Efficiency > C408 System Commissioning > C408.3 Lighting System Functional Testing > C408.3.1 Functional Testing > C408.3.1.2 Time-Switch Controls