A5.209.1 Lighting Control Devices,
ballasts and luminaires. Any lighting control device, ballast or luminaire subject to the requirements of Section A5.209 shall be installed only if the manufacturer has certified to the Commission that the device complies with all of the applicable requirements of Section A5.209.
Lighting control devices may be individual devices or systems consisting of two or more components. For control systems consisting of two or more components, such as an Energy Management Control System (EMCS), the manufacturer of the control system shall certify each of the components required for the system to comply with Section A5.209.
ULTRASOUND MAXIMUM DECIBEL VALUES
MIDFREQUENCY OF SOUND PRESSURE THIRD-OCTAVE BAND (in kHz) | MAXIMUM dB LEVEL WITHIN THIRD-OCTAVE BAND (in dB reference 20 micropascals) |
Less than 20 | 80 |
20 or more to less than 25 | 105 |
25 or more to less than 31.5 | 110 |
31.5 or more | 115 |
Automatic time switch control devices or system shall:
- Be capable of programming different schedules for weekdays and weekends; and
- Have program backup capabilities that prevent the loss of the device's schedules for at least 7 days and the device's time and date setting for at least 72 hours if power is interrupted.
If the device emits ultrasonic radiation as a signal for sensing occupants within an area, the device shall:
- Have had a Radiation Safety Abbreviated Report submitted to the Center for Devices and Radiological Health, Federal Food and Drug Administration, under 21 Code of Federal Regulations, Section 1002.12 (1996) and a copy of the report shall have been submitted to the California Energy Commission; and
- Emit no audible sound; and
- Not emit ultrasound in excess of the decibel (dB) values shown in Table A5.209.1-A, measured no more than 5 feet from the source, on axis.
If the device emits microwave radiation as a signal for sensing occupants within the area, the device shall:
- Comply with all applicable provisions in 47 Code of Federal Regulations, Parts 2 and 15 (1996) and have an approved Federal Communications Commission Identifier that appears on all units of the device and that has been submitted to the California Energy Commission; and
- Not emit radiation in excess of 1 milliwatt per square centimeter measured at no more than 5 centimeters from the emission surface of the device; and
- Have permanently affixed to it installation instructions recommending that it be installed at least 12 inches from any area normally used by room occupants.
Multilevel occupant sensors shall have an automatic OFF function that turns off all the lights and either an automatic or a manually controlled ON function capable of meeting all the multilevel and uniformity requirements of Section A5.209.2.2 for the controlled lighting. The first stage shall be capable of activating between 30—70 percent of the lighting power in a room either through an automatic or manual action and may be a switching or dimming system. After that event occurs the device shall be capable of all of the following actions when manually called to do so by the occupant:
- Activating the alternate set of lights.
- Activating 100 percent of the lighting power.
- Deactivating all lights.
Automatic daylighting control devices used to control lights in daylit zones shall:
- Be capable of reducing the power consumption of the general lighting in the controlled area by at least two thirds in response to the availability of daylight; and
- If the device is a dimmer controlling incandescent or fluorescent lamps, provide electrical outputs to lamps for reduced flicker operation through the dimming range, so that the light output has an amplitude modulation of less than 30 percent for frequencies less than 200 Hz and without causing premature lamp failure; and
- If the devices reduce lighting in control steps, incorporate time-delay circuits to prevent cycling of light level changes of less than 3 minutes and have a manual or automatic means of adjusting the deadband to provide separation of on and off points for each control step; and
- If the device is placed in calibration mode, automatically restore its time delay settings to normal operation programmed time delays after no more than 60 minutes; and
- Have a setpoint control that easily distinguishes settings to within 10 percent of full scale adjustment; and
- Have a light sensor that has a linear response with 5 percent accuracy over the range of illuminance measured by the light sensor; and
- Have a light sensor that is physically separated from where calibration adjustments are made or is capable of being calibrated in a manner that the person initiating calibration is remote from the sensor during calibration to avoid influencing calibration accuracy.
Multilevel astronomical time-switch controls used to control lighting in daylit zones shall:
- Contain at least two separately programmable steps per zone that reduces illuminance in a relatively uniform manner as specified in Section A5.209.2.2; and
- Have a separate offset control for each step of 1 to 240 minutes; and
- Have sunrise and sunset prediction accuracy within +/- 15 minutes and timekeeping accuracy within 5 minutes per year; and
- Store astronomical time parameters (used to develop longitude, latitude, time zone) for at least 7 days if power is interrupted; and
- Display date/time, sunrise and sunset and switching times for each step; and
- Have an automatic daylight savings time adjustment; and
- Have automatic time switch capabilities specified in Section A5.209.1.3.
Outdoor astronomical time-switch controls used to control outdoor lighting as specified in Section A5.209.3.3 shall:
- Contain at least two separately programmable steps per function area; and
- Have the ability to independently offset the on and off times for each channel by 0 to 99 minutes before or after sunrise or sunset; and
- Have sunrise and sunset prediction accuracy within +/- 15 minutes and timekeeping accuracy within 5 minutes per year; and
- Store astronomical time parameters (used to develop longitude, latitude, time zone) for at least 7 days if power is interrupted; and
- Display date/time, sunrise and sunset; and
- Have an automatic daylight savings time adjustment; and
- Have automatic time switch capabilities specified in Section A5.209.1.3.
Dimmers used to control lighting shall:
- Be capable of reducing power consumption by a minimum of 65 percent when the dimmer is at its lowest light level; and
- If the device is a dimmer controlling incandescent or fluorescent lamps, provide electrical outputs to lamps for reduced flicker operation through the dimming range, so that the light output has an amplitude modulation of less than 30 percent for frequencies less than 200 Hz and without causing premature lamp failure; and
- Be listed by a rating lab recognized by the International Code Council (ICC) as being in compliance with Underwriters Laboratories Standards; and
- If the device is a wall box dimmer designed to be used in a three- or more-way circuit with nondimmable switches, the level set by the dimmer, shall not be overridden by any of the switches in the circuit. The dimmer and all of the switches in the circuit shall have the capability of turning lighting OFF if it is ON and turning lighting ON to the level set by the dimmer if the lighting is OFF. Any wall box dimmer that is connected to a system with an emergency override function shall be controlled by the emergency override.
- If the device is a stepped dimmer, it shall include an off position to turn lights completely off.