Code calculators: Code Calculators automatically generates a detailed list of requirements.
REFERENCE
Amendment Styling
Industry-leading search
Code diagrams
RESEARCH
Code calculators
Filter by topic
Code compare
Code sheet exports
COLLABORATION
Team projects
Bookmarks
Comments
START 2 WEEK FREE TRIAL
Have an account? Sign in
// CODE SNIPPET

Section 2610 Light-Transmitting Plastic Skylight Glazing

Building Code 2018 of Illinois > 26 Plastic > 2610 Light-Transmitting Plastic Skylight Glazing
JUMP TO FULL CODE CHAPTER

2610.1 Light-Transmitting Plastic Glazing of Skylight Assemblies

Skylight assemblies glazed with light-transmitting plastic shall conform to the provisions of this section and Section 2606. Unit skylights glazed with light-transmitting plastic shall comply with Section 2405.5.
Exception: Skylights in which the light-transmitting plastic conforms to the required roof-covering class in accordance with Section 1505.

2610.2 Mounting

The light-transmitting plastic shall be mounted above the plane of the roof on a curb constructed in accordance with the requirements for the type of construction classification, but not less than 4 inches (102 mm) above the plane of the roof. Edges of the light-transmitting plastic skylights or domes shall be protected by metal or other approved noncombustible material, or the light transmitting plastic dome or skylight shall be shown to be able to resist ignition where exposed at the edge to a flame from a Class B brand as described in ASTM E108 or UL 790. The Class B brand test shall be conducted on a skylight that is elevated to a height as specified in the manufacturer's installation instructions, but not less than 4 inches (102 mm).
Exceptions:
  1. Curbs shall not be required for skylights used on roofs having a minimum slope of three units vertical in 12 units horizontal (25-percent slope) in occupancies in Group R-3 and on buildings with a nonclassified roof covering.
  2. The metal or noncombustible edge material is not required where nonclassified roof coverings are permitted.

2610.3 Slope

Flat or corrugated light-transmitting plastic skylights shall slope not less than four units vertical in 12 units horizontal (4:12). Dome-shaped skylights shall rise above the mounting flange a minimum distance equal to 10 percent of the maximum width of the dome but not less than 3 inches (76 mm).
Exception: Skylights that pass the Class B Burning Brand Test specified in ASTM E108 or UL 790.

2610.4 Maximum Area of Skylights

ILLUSTRATION
Each skylight shall have a maximum area within the curb of 100 square feet (9.3 m2).
Exception: The area limitation shall not apply where the building is equipped throughout with an automatic sprinkler system in accordance with Section 903.3.1.1 or the building is equipped with smoke and heat vents in accordance with Section 910.

2610.5 Aggregate Area of Skylights

The aggregate area of skylights shall not exceed 331/3 percent of the floor area of the room or space sheltered by the roof in which such skylights are installed where Class CC1 materials are utilized, and 25 percent where Class CC2 materials are utilized.
Exception: The aggregate area limitations of light-transmitting plastic skylights shall be increased 100 percent beyond the limitations set forth in this section where the building is equipped throughout with an automatic sprinkler system in accordance with Section 903.3.1.1 or the building is equipped with smoke and heat vents in accordance with Section 910.

2610.6 Separation

Skylights shall be separated from each other by a distance of not less than 4 feet (1219 mm) measured in a horizontal plane.
Exceptions:
  1. Buildings equipped throughout with an automatic sprinkler system in accordance with Section 903.3.1.1.
  2. In Group R-3, multiple skylights located above the same room or space with a combined area not exceeding the limits set forth in Section 2610.4.

2610.7 Location

Where exterior wall openings are required to be protected in accordance with Section 705, a skylight shall not be installed within 6 feet (1829 mm) of such exterior wall.

2610.8 Combinations of Roof Panels and Skylights

Combinations of light-transmitting plastic roof panels and skylights shall be subject to the area and percentage limitations and separation requirements applicable to roof panel installations.

Related Code Sections


Section 2610 Plastic, Light-Transmitting Plastic Skylight Glazing
Skylight assemblies glazed with light-transmitting plastic shall conform to the provisions of this section and Section 2606. Unit skylights glazed ...
Building Code 2018 of Illinois > 26 Plastic > 2610 Light-Transmitting Plastic Skylight Glazing
Section 2610 Plastic, Light-Transmitting Plastic Skylight Glazing
Skylight assemblies glazed with light-transmitting plastic shall conform to the provisions of this section and Section 2606.  Exception ...
Building Code 2021 of Illinois > 26 Plastic > 2610 Light-Transmitting Plastic Skylight Glazing
2610.1 Plastic, Light-Transmitting Plastic Glazing of Skylight Assemblies
Skylight assemblies glazed with light-transmitting plastic shall conform to the provisions of this section and Section 2606. Unit skylights glazed ...
Building Code 2018 of Illinois > 26 Plastic > 2610 Light-Transmitting Plastic Skylight Glazing > 2610.1 Light-Transmitting Plastic Glazing of Skylight Assemblies
2610.1 Plastic, Light-Transmitting Plastic Glazing of Skylight Assemblies
Skylight assemblies glazed with light-transmitting plastic shall conform to the provisions of this section and Section 2606.  Exception ...
Building Code 2021 of Illinois > 26 Plastic > 2610 Light-Transmitting Plastic Skylight Glazing > 2610.1 Light-Transmitting Plastic Glazing of Skylight Assemblies
2610.8 Plastic, Combinations of Roof Panels and Skylights
Combinations of light-transmitting plastic roof panels and skylights shall be subject to the area and percentage limitations and separation ...
Building Code 2021 of Illinois > 26 Plastic > 2610 Light-Transmitting Plastic Skylight Glazing > 2610.8 Combinations of Roof Panels and Skylights
Help Contact Us Privacy Terms
Code diagrams
Code diagrams
Unpack the code through illustrations and descriptions.
Search
Search
Don't miss relevant code. Quickly locate sections across your jurisdiction.
Code sheet exports
Code sheet exports
Generate a code sheet that integrates with your drawing set.
Code Calculators
Code Calculators
Code calculators automatically generate a detailed list of requirements.
Code Compare
Code Compare
Highlight differences between any two building codes.
Shared projects
Shared projects
Projects provide a dedicated space to collaborate on code research.
UpCodes Premium
Leverage the most sophisticated code compliance platform.
VISIT PRICING
UpCodes Premium
Leverage the full code compliance platform.
START 2 WEEK FREE TRIAL PRICING