Signs or displays utilizing LED display panels shall comply with this section of the code.
  1. Panels used for LED displays shall be listed appliances.
  2. Panel displays under 100 square feet in aggregate area shall not require any additional protection.
  3. Panel displays between 100 square feet and 500 square feet in aggregate area shall be located in a space protected by an automatic sprinkler system.
  4. Panel displays exceeding 500 square feet and below 1,000 square feet in aggregate area shall be protected with a water curtain complying with NFPA 13 across the exposed face of the display or be located in a space protected with an automatic sprinkler system of at least Ordinary Hazard Group 2.
  5. Panel displays of 1,000 or greater square feet in aggregate area shall be protected by a water curtain complying with NFPA 13 across the exposed face of the display.
  6. For panel displays exceeding 500 square feet, a Fire Protection Report shall be provided to substantiate the preceding requirements are met.

Related Code Sections

2611.5 Plastic, LED Display Panels
Signs or displays utilizing LED display panels shall comply with this section of the code. Panels used for LED displays shall be listed ...
918.3.2.1 Fire Protection and Life Safety Systems, Graphic Display
, where a section view of the tower can be allowed in conjunction with plan views of typical tower floors. At a minimum, the panel must satisfy ...
909.21.2.1 Fire Protection and Life Safety Systems, Graphic Display
of the tower can be allowed in conjunction with plan views of typical tower floors. At a minimum, the panel must satisfy the following requirements ...
909.21.3.3 Fire Protection and Life Safety Systems, LED Legend:
A legend of LED's shall be provided. The legend LED shall continuously be lit. The legend shall indicate the following colors and labels: Red LED ...