• Codes
  • Features

    Features Overview

    Go to features
    Reference

    Reference.

    A reliable and up-to-date source of codes.
    Research

    Research.

    Rapidly and efficiently calculate project parameters.
    Collaboration

    Collaboration.

    Get everyone on the same page and streamline code research.
    Workflows
    Architects
    Architects
    General Contractors
    General Contractors
    Building Official & Plans Examiners
    Building Official & Plans Examiners
    Inspectors
    Inspectors
    Owners
    Owners
    Subcontractors
    Subcontractors
    Code Consultants
    Code Consultants
  • Pricing
  • Login
  • Sign Up
Sign Up
Login
  • Code Library
  • Features
  • Pricing
  • About
  • Careers
  • Help
  • Contact
  • Terms
  • Privacy
Sign Up
Upgrade to Premium
Code calculators: Code Calculators automatically generates a detailed list of requirements.
REFERENCE
Amendment Styling
Industry-leading search
Code diagrams
RESEARCH
Code calculators
Filter by topic
Code compare
Code sheet exports
COLLABORATION
Team projects
Bookmarks
Comments
START 2 WEEK FREE TRIAL
Have an account? Sign in
// CODE SNIPPET

Section 2510 Lathing and Furring for Cement Plaster (Stucco)

Building Code 2018 of Illinois > 25 Gypsum Board, Gypsum Panel Products and Plaster > 2510 Lathing and Furring for Cement Plaster (Stucco)
JUMP TO FULL CODE CHAPTER

2510.1 General

Exterior and interior cement plaster and lathing shall be done with the appropriate materials listed in Table 2507.2 and Chapter 35.

2510.2 Weather Protection

Materials shall be stored in such a manner as to protect them from the weather.

2510.3 Installation

Installation of these materials shall be in compliance with ASTM C926 and ASTM C1063.

2510.4 Corrosion Resistance

Metal lath and lath attachments shall be of corrosion-resistant material.

2510.5 Backing

Backing or a lath shall provide sufficient rigidity to permit plaster applications.

2510.5.1 Support of Lath

Where lath on vertical surfaces extends between rafters or other similar projecting members, solid backing shall be installed to provide support for lath and attachments.

2510.5.2 Use of Gypsum Backing Board

Gypsum backing for cement plaster shall be in accordance with Section 2510.5.2.1 or 2510.5.2.2.

2510.5.2.1 Gypsum Board as a Backing Board

Gypsum lath or gypsum wallboard shall not be used as a backing for cement plaster.
Exception: Gypsum lath or gypsum wallboard is permitted, with a water-resistive barrier, as a backing for self-furred metal lath or self-furred wire fabric lath and cement plaster where either of the following conditions occur:
  1. On horizontal supports of ceilings or roof soffits.
  2. On interior walls.

2510.5.2.2 Gypsum Sheathing Backing

Gypsum sheathing is permitted as a backing for metal or wire fabric lath and cement plaster on walls. A water-resistive barrier shall be provided in accordance with Section 2510.6.

2510.5.3 Backing Not Required

Wire backing is not required under expanded metal lath or paperbacked wire fabric lath.

2510.6 Water-Resistive Barriers

Water-resistive barriers shall be installed as required in Section 1403.2 and, where applied over wood-based sheathing, shall include a water-resistive vapor-permeable barrier with a performance at least equivalent to two layers of water-resistive barrier complying with ASTM E2556, Type I. The individual layers shall be installed independently such that each layer provides a separate continuous plane and any flashing (installed in accordance with Section 1404.4) intended to drain to the water-resistive barrier is directed between the layers.
Exceptions:
  1. Where the water-resistive barrier that is applied over wood-based sheathing has a water resistance equal to or greater than that of a water-resistive barrier complying with ASTM E2556, Type II and is separated from the stucco by an intervening, substantially nonwater-absorbing layer or drainage space.
  2. Where the water-resistive barrier is applied over wood-based sheathing in Climate Zone 1A, 2A or 3A, a ventilated air space shall be provided between the stucco and water-resistive barrier.

2510.7 Preparation of Masonry and Concrete

Surfaces shall be clean, free from efflorescence, sufficiently damp and rough for proper bond. If the surface is insufficiently rough, approved bonding agents or a Portland cement dash bond coat mixed in proportions of not more than two parts volume of sand to one part volume of Portland cement or plastic cement shall be applied. The dash bond coat shall be left undisturbed and shall be moist cured not less than 24 hours.

Related Code Sections


Section 2510 Gypsum Board, Gypsum Panel Products and Plaster, Lathing and Furring for Cement Plaster (Stucco)
-furred wire fabric lath and cement plaster where either of the following conditions occur: On horizontal supports of ceilings or roof soffits. On ...
Building Code 2018 of Illinois > 25 Gypsum Board, Gypsum Panel Products and Plaster > 2510 Lathing and Furring for Cement Plaster (Stucco)
Section 2510 Gypsum Board, Gypsum Panel Products and Plaster, Lathing and Furring for Cement Plaster (Stucco)
or self-furred wire fabric lath and cement plaster where either of the following conditions occur: On horizontal supports of ceilings or roof soffits ...
Building Code 2021 of Illinois > 25 Gypsum Board, Gypsum Panel Products and Plaster > 2510 Lathing and Furring for Cement Plaster (Stucco)
2510.1 Gypsum Board, Gypsum Panel Products and Plaster, General
Exterior and interior cement plaster and lathing shall be done with the appropriate materials listed in Table 2507.2 and Chapter 35 ...
Building Code 2018 of Illinois > 25 Gypsum Board, Gypsum Panel Products and Plaster > 2510 Lathing and Furring for Cement Plaster (Stucco) > 2510.1 General
2510.7 Gypsum Board, Gypsum Panel Products and Plaster, Preparation of Masonry and Concrete
bonding agents or a Portland cement dash bond coat mixed in proportions of not more than two parts volume of sand to one part volume of Portland cement ...
Building Code 2021 of Illinois > 25 Gypsum Board, Gypsum Panel Products and Plaster > 2510 Lathing and Furring for Cement Plaster (Stucco) > 2510.7 Preparation of Masonry and Concrete
2510.7 Gypsum Board, Gypsum Panel Products and Plaster, Preparation of Masonry and Concrete
bonding agents or a Portland cement dash bond coat mixed in proportions of not more than two parts volume of sand to one part volume of Portland cement ...
Building Code 2018 of Illinois > 25 Gypsum Board, Gypsum Panel Products and Plaster > 2510 Lathing and Furring for Cement Plaster (Stucco) > 2510.7 Preparation of Masonry and Concrete
Help Contact Us Privacy Terms
Code Compare
Code Compare
Highlight differences between any two building codes.
Shared projects
Shared projects
Projects provide a dedicated space to collaborate on code research.
Code sheet exports
Code sheet exports
Generate a code sheet that integrates with your drawing set.
Search
Search
Don't miss relevant code. Quickly locate sections across your jurisdiction.
Code Calculators
Code Calculators
Code calculators automatically generate a detailed list of requirements.
Code diagrams
Code diagrams
Unpack the code through illustrations and descriptions.
UpCodes Premium
Leverage the most sophisticated code compliance platform.
VISIT PRICING
UpCodes Premium
Leverage the full code compliance platform.
START 2 WEEK FREE TRIAL PRICING