3305.3.2.3 Lateral Concrete Pressure
JUMP TO FULL CODE CHAPTER
Design of forms, ties and bracing shall satisfy the minimum lateral pressures of fresh concrete specified in Table 3305.3.2.3.
TABLE 3305.3.2.3 MINIMUM LATERAL PRESSURES TO BE ASSUMED FOR FRESH CONCRETE WEIGHING 150 POUNDS PER CUBIC FOOT a, b, c
TABLE 3305.3.2.3 MINIMUM LATERAL PRESSURES TO BE ASSUMED FOR FRESH CONCRETE WEIGHING 150 POUNDS PER CUBIC FOOT a, b, c
TYPE OF WORK | MINIMUM LATERAL PRESSURE ASSUMED (PSF) | LIMITATIONS |
Columns: Ordinary work with normal internal vibration | p = 150 + (9000R/T) | Maximum 3,000 psf or 150h, whichever is less |
Walls: Rate of placement at 7 feet per hour or less | p = 150 + (9000R/T) | Maximum 2,000 psf or 150h, whichever is less |
Walls: Rate of placement at greater than 7 feet per hour | p = 150 + (43400/T) + (2800R/T) | Maximum 2,000 psf or 150h, whichever is less |
Slabs | p = 150h | None |
For SI: 1 inch = 25.4 mm, 1 foot per second = 0.305 m/s, 1 pound per cubic foot = 16.02 kg/m3, 1 pound per square foot = 4.882 kg/m2, °C = (°F-32)/1.8. |
where: |
R = rate of placement, feet per hour. |
T = temperature of concrete in the forms, °F. |
h = height of fresh concrete above point considered, feet. |
a. Allowances for change in lateral pressure shall be made for concrete weighing other than 150 pcf; for concrete containing pozzolanic additions or cements other than Type I, for concrete having slumps greater than 6 inches, or for concrete consolidated by revibration or external vibration of forms. |
b. Where retarding admixtures are employed under hot weather conditions, an effective value of temperature less than that of the concrete in the forms shall be used in the above formula. |
c. If retarding admixtures are used in cold weather, the lateral pressure may be assumed as that exerted by a fluid weighing 150 pcf. |
Related Code Sections
1906.3.2 Concrete, Lateral Concrete Pressure
Design of forms, ties, and bracing shall satisfy the minimum lateral pressures of fresh concrete specified in Table 1906.3.2.
TABLE ...
NYC Building Code 2008 > 19 Concrete > 1906 Formwork, Embedded Pipes and Construction Joints > 1906.3 Design of Concrete Formwork > 1906.3.2 Lateral Concrete Pressure
3305.3.2.3 Safeguards During Construction or Demolition, Lateral Concrete Pressure
Design of forms, ties and bracing shall satisfy the minimum lateral pressures of fresh concrete specified in Table 3305.3.2.3. TABLE 3305.3.2.3 ...
NYC Building Code 2014 > 33 Safeguards During Construction or Demolition > 3305 Material Placement and Installation > 3305.3 Concrete Formwork > 3305.3.2 Design of Concrete Formwork > 3305.3.2.3 Lateral Concrete Pressure
1810.3.3 Soils and Foundations, Installation
of the liner at a sufficient height to offset any hydrostatic or lateral soil pressure.
Where grout is placed by pumping through a hollow ...
NYC Building Code 2008 > 18 Soils and Foundations > 1810 Cast-In-Place Concrete Pile Foundations > 1810.3 Drilled or Augered Uncased Piles > 1810.3.3 Installation
1810.3.3 Soils and Foundations, Installation
of the liner at a sufficient height to offset any hydrostatic or lateral soil pressure. Where grout is placed by pumping through a hollow-stem auger ...
NYC Building Code 2014 > 18 Soils and Foundations > 1810 Cast-In-Place Concrete Piles > 1810.3 Drilled or Augered Uncased Piles > 1810.3.3 Installation
1807.3.2 Soils and Foundations, Walls
Walls required to be waterproofed shall be of concrete or masonry and shall be designed and constructed to withstand the hydrostatic pressures ...
NYC Building Code 2008 > 18 Soils and Foundations > 1807 Dampproofing and Waterproofing > 1807.3 Waterproofing Required > 1807.3.2 Walls