C402.2 Large Cracks and Joints
JUMP TO FULL CODE CHAPTER
Cracks with widths larger than 1/16 inch (1.6 mm) shall be enlarged to a recess with minimum dimensions of 1/4 inch by 1/4 inch (6 mm by 6 mm) and sealed with an approved caulk or sealant applied over a sealant backer in accordance with the manufacturer's recommendations. Cracks and joints with widths less than 1/16 inch (1.6 mm) may also be sealed in this manner if traffic, floor covering material or other conditions are inconsistent with the provisions of Section C402.1.
Related Code Sections
C402.2 Florida Standard for Mitigation of Radon in Existing Buildings, Large Cracks and Joints
Cracks with widths larger than 1 / 16 inch (1.6 mm) shall be enlarged to a recess with minimum dimensions of 1 / 4 inch by 1 / 4 inch (6 mm ...
2017 FBC - Building, 6th edition > C Florida Standard for Mitigation of Radon in Existing Buildings > C402 Sealing Cracks and Joints in Concrete Floors and Walls > C402.2 Large Cracks and Joints
C402.2 Florida Standard for Mitigation of Radon in Existing Buildings, Large Cracks and Joints
Cracks with widths larger than 1 / 16 inch (1.6 mm) shall be enlarged to a recess with minimum dimensions of 1 / 4 inch by 1 / 4 inch (6 mm ...
2020 FBC - Building, 7th edition > C Florida Standard for Mitigation of Radon in Existing Buildings > C4 Structural Sealing and HVAC System Balancing > C402 Sealing Cracks and Joints in Concrete Floors and Walls > C402.2 Large Cracks and Joints
E402.2 Florida Standard for Mitigation of Radon in Existing Buildings Effective: June 1, 1994, Large Cracks and Joints
Cracks with widths larger than 1 / 16 inch (1.6 mm) shall be enlarged to a recess with minimum dimensions of 1 / 4 inch by 1 / 4 inch (6 mm ...
2020 FBC - Residential, 7th edition > E Florida Standard for Mitigation of Radon in Existing Buildings Effective: June 1, 1994 > E402 Sealing Cracks and Joints in Concrete Floors and Walls > E402.2 Large Cracks and Joints
E303.3.2 Florida Standard for Radon-Resistant New Commercial Construction, Joints
as specified above. The lap joint shall be sufficiently large to prevent failure of the sealant or waterstop, but in no case shall the sealant reservoir be less ...
2017 FBC - Building, 6th edition > E Florida Standard for Radon-Resistant New Commercial Construction > E303 Concrete Floors in Contact With Soil Gas. > E303.3 Sealing of Construction Joints, Penetrations, Cracks, and Other Connections > E303.3.2 Joints
E303.3.2 Florida Standard for Radon-Resistant New Commercial Construction, Joints
as specified above. The lap joint shall be sufficiently large to prevent failure of the sealant or waterstop, but in no case shall the sealant reservoir be less ...
2020 FBC - Building, 7th edition > E Florida Standard for Radon-Resistant New Commercial Construction > E301 Construction Requirements Forpassive Controls > E303 Concrete Floors in Contact With Soil Gas > E303.3 Sealing of Construction Joints, Penetrations, Cracks, and Other Connections > E303.3.2 Joints