1010.1.5 Landings at Doors
Go To Full Code Chapter
Landings shall have a width not less than the width of the stairway or the door, whichever is greater. Doors in the fully open position shall not reduce a required dimension by more than 7 inches (178 mm). Where a landing serves an occupant load of 50 or more, doors in any position shall not reduce the landing to less than one-half its required width. Landings shall have a length measured in the direction of travel of not less than 44 inches (1118 mm).
Upcodes Diagrams
Related Code Sections
1010.1.5 Means of Egress, Landings at Doors
Landings shall have a width not less than the width of the stairway or the door, whichever is greater. Doors in the fully open position shall ...
1010.1.6 Means of Egress, Landings at Doors
Landings shall have a width not less than the width of the stairway or the door, whichever is greater. Doors in the fully open position shall ...
5.4.2.4 Special Application Elevators, Clearance Between Landing Doors or Gates and Landing Sills and Car Doors or Gates
Clearances shall conform to 5.3.1.8.2 ...
5.12.1.2 Special Application Elevators,
Global Essential Safety Requirement 3.1.6, Locking Landing Doors and Closing LCU (Car) Doors, shall not apply. Movement of the car shall be permitted ...
5.3.1.19.2.2 Special Application Elevators, Monitoring of the Car Door or Gate Switch Electric Contacts
The elevator controls shall be designed in such a manner that when the car stops at a floor and the landing door or gate and its related electric ...
Safety Code for Elevators and Escalators 2019 of Illinois > 5 Special Application Elevators > 5.3 Private Residence Elevators > 5.3.1 Private Residence Electric Elevators > 5.3.1.19 Operating Devices and Control Equipment > 5.3.1.19.2 Control and Operating Circuit Requirements > 5.3.1.19.2.2 Monitoring of the Car Door or Gate Switch Electric Contacts