13.6.3.1.3.9 Label Visibility
Go To Full Code Chapter
13.6.3.1.3.9.1
Fire extinguishers shall be installed so that the
fire extinguisher's operating instructions face outward.
[10:6.1.3.9.1]
13.6.3.1.3.9.2
Hazardous materials identification systems
(HMIS) labels, 6-year maintenance labels, hydrostatic test
labels, or other labels shall not be located or placed on the
front of the extinguisher. [10:6.1.3.9.2]
13.6.3.1.3.9.3
The restrictions of 13.6.3.1.3.9.2 shall not apply
to the original manufacturer's labels, labels that specifically
relate to the extinguisher's operation or fire classification, or
inventory control labels specific to that extinguisher.
[10:6.1.3.9.3]