Section 506 Key Boxes

California Fire Code 2016 > 5 Fire Service Features > 506 Key Boxes
JUMP TO FULL CODE CHAPTER

506.1 Where required

Where access to or within a structure or an area is restricted because of secured openings or where immediate access is necessary for life-saving or fire-fighting purposes, the fire code official is authorized to require a key box to be installed in an approved location. The key box shall be of an approved type listed in accordance with UL 1037, and shall contain keys to gain necessary access as required by the fire code official.

506.1.1 Locks

An approved lock shall be installed on gates or similar barriers where required by the fire code official.

506.1.2 Key boxes for nonstandardized fire service elevator keys

Key boxes provided for nonstandardized fire service elevator keys shall comply with Section 506.1 and all of the following:

  1. The key box shall be compatible with an existing rapid entry key box system in use in the jurisdiction and approved by the fire code official.
  2. The front cover shall be permanently labeled with the words “Fire Department Use Only—Elevator Keys.”
  3. The key box shall be mounted at each elevator bank at the lobby nearest to the lowest level of fire department access.
  4. The key box shall be mounted 5 feet 6 inches (1676 mm) above the finished floor to the right side of the elevator bank.
  5. Contents of the key box are limited to fire service elevator keys. Additional elevator access tools, keys and information pertinent to emergency planning or elevator access shall be permitted where authorized by the fire code official.
  6. In buildings with two or more elevator banks, a single key box shall be permitted to be used where such elevator banks are separated by not more than 30 feet (9144 mm). Additional key boxes shall be provided for each individual elevator or elevator bank separated by more than 30 feet (9144 mm).

Exception: A single key box shall be permitted to be located adjacent to a fire command center or the nonstandard fire service elevator key shall be permitted to be secured in a key box used for other purposes and located in accordance with Section 506.1.

506.2 Key box maintenance

The operator of the building shall immediately notify the fire code official and provide the new key where a lock is changed or rekeyed. The key to such lock shall be secured in the key box.
Share URL

Copy and paste the link below into emails, chats or browsers.

Copy

You can also copy or bookmark the link from your browser's address bar.

Related Code Sections


3310.2 Fire Safety During Construction and Demolition, Key boxes
Key boxes shall be provided as required by Chapter 5 ...
California Fire Code 2016 > 33 Fire Safety During Construction and Demolition > 3310 Access for Fire Fighting > 3310.2 Key boxes
Section 506 Fire Service Features, Key Boxes
or where immediate access is necessary for life-saving or fire-fighting purposes, the fire code official is authorized to require a key box ...
California Fire Code 2016 > 5 Fire Service Features > 506 Key Boxes
502.1 Fire Service Features, Definitions
LANE. KEY BOX. TRAFFIC CALMING DEVICES ...
California Fire Code 2016 > 5 Fire Service Features > 502 Definitions > 502.1 Definitions
Section 3310 Fire Safety During Construction and Demolition, Access for Fire Fighting
Key boxes shall be provided as required by Chapter 5 ...
California Fire Code 2016 > 33 Fire Safety During Construction and Demolition > 3310 Access for Fire Fighting
1910.262(p)(1) Special Industries, J-box protection
Each valve controlling the flow of steam, injurious gases, or liquids into a J-box shall be equipped with a chain, lock, and key, so that any worker ...
OSHA 1910 General Industry > R Special Industries > 1910.262 Textiles > 1910.262(p) Continuous bleach range (cotton and rayon) > 1910.262(p)(1) J-box protection
About UpCodes

UpCodes provides an intuitive resource to navigate building regulations.

Codes are organized by jurisdiction to help you understand which regulations apply to your project.


Find Your Codes
COMPANY INFO About Contact Careers Terms Privacy
CATEGORY General New York City New York State California Codes Building Codes Online
PREMIUM Features Pricing Sign Up Log In
CODES IBC 2015 IRC 2015 IPC 2015 California Building Code 2016 Popular Sections

FOLLOW US