1211.13 Joints Between Various Materials
JUMP TO FULL CODE CHAPTER
Joints between
various materials shall be installed in accordance with the
manufacturer's installation instructions and shall comply with
Section 1211.13.1 and Section 1211.13.2.
Joints from copper or copper alloy
pipe or tubing to threaded pipe shall be made by the use of
copper alloy adapter, copper alloy nipple [minimum 6
inches (152 mm)], dielectric fitting, or dielectric union in
accordance with ASSE 1079. The joint between the copper
or copper alloy pipe or tubing and the fitting shall be
a soldered, brazed, flared, or pressed joint and the connection
between the threaded pipe and the fitting shall be
made with a standard pipe size threaded joint.
Where connecting
plastic pipe to other types of piping, approved
types of adapter or transition fittings designed for the
specific transition intended shall be used.
Related Code Sections
1211.13 Hydronics, Joints Between Various Materials
Joints between
various materials shall be installed in accordance with the
manufacturer's installation instructions and shall comply with
Section ...
Los Angeles Mechanical Code > 12 Hydronics > 1211.0 Joints and Connections > 1211.13 Joints Between Various Materials
1211.14 Hydronics, Joints Between Various Materials
Joints between various materials shall be installed in accordance
with the manufacturer's installation instructions and shall
comply with Section ...
Los Angeles Mechanical Code > 12 Hydronics > 1211.0 Joints and Connections > 1211.14 Joints Between Various Materials
605.16 Water Supply and Distribution, Joints Between Various Materials
Joints
between various materials shall be installed in accordance
with the manufacturer's installation instructions and shall
comply with Section ...
Los Angeles Plumbing Code > 6 Water Supply and Distribution > 605.0 Joints and Connections > 605.16 Joints Between Various Materials
705.10 Sanitary Drainage, Joints Between Various Materials
Joints
between various materials shall be installed in accordance
with the manufacturer's installation instructions and with Section
705.10.1 through ...
Los Angeles Plumbing Code > 7 Sanitary Drainage > 705.0 Joints and Connections > 705.10 Joints Between Various Materials
705.10.4 Sanitary Drainage, Stainless Steel Pipe to Other Materials
Where connecting stainless steel pipe to other types of
piping, listed mechanical joints of the compression type
and listed for the specific ...
Los Angeles Plumbing Code > 7 Sanitary Drainage > 705.0 Joints and Connections > 705.10 Joints Between Various Materials > 705.10.4 Stainless Steel Pipe to Other Materials