// CODE SNIPPET
715.8 Joints and Voids in Smoke Barriers
Go To Full Code Chapter
Fire-resistant joint systems protecting joints in smoke barriers, and perimeter fire containment systems protecting voids at the intersection of a horizontal smoke barrier and an exterior curtain wall, shall be tested in accordance with the requirements of UL 2079 for air leakage. The L rating of the joint system shall not exceed 5 cubic feet per minute per linear foot (0.00775 m3/s m) of joint at 0.30 inch (74.7 Pa) of water for both the ambient temperature and elevated temperature tests.
Related Code Sections
715.8 Fire and Smoke Protection Features, Joints and Voids in Smoke Barriers
Fire-resistant joint systems protecting joints in smoke barriers, and perimeter fire containment systems protecting voids ...
705.9.1 Fire and Smoke Protection Features, Voids
The void created at the intersection of a floor/ceiling assembly and an exterior curtain wall assembly shall be protected in accordance with Section ...
705.9.1 Fire and Smoke Protection Features, Voids
The void created at the intersection of a floor/ceiling assembly and an exterior curtain wall assembly shall be protected in accordance with Section ...
707.9 Fire and Smoke Protection Features, Voids at Intersections
The voids created at the intersection of a fire barrier and a nonfire-resistance-rated roof assembly or a nonfire-resistance-rated exterior wall ...
707.9 Fire and Smoke Protection Features, Voids at Intersections
The voids created at the intersection of a fire barrier and a nonfire-resistance-rated roof assembly or a nonfire-resistance-rated exterior wall ...