Section 704 Joints and Voids
JUMP TO FULL CODE CHAPTER
Where required when the building was originally constructed, materials and systems used to protect joints and voids in the following locations shall be maintained. The materials and systems shall be securely attached to or bonded to the adjacent construction, without openings visible through the construction.
- Joints in or between fire-resistance-rated walls, floors or floor/ceiling assemblies and roof or roof/ceiling assemblies.
- Joints in smoke barriers.
- Voids at the intersection of a horizontal floor assembly and an exterior curtain wall.
- Voids at the intersection of a horizontal smoke barrier and an exterior curtain wall.
- Voids at the intersection of a nonfire-resistance-rated floor assembly and an exterior curtain wall.
- Voids at the intersection of a vertical fire barrier and an exterior curtain wall.
- Voids at the intersection of a vertical fire barrier and a nonfire-resistance-rated roof assembly.
Unprotected joints and voids do not need to be protected where such joints and voids were not required to be protected when the building was originally constructed.
Where openings are required to be protected, opening protectives shall be maintained self-closing or automatic-closing by smoke detection. Existing fusible-link-type automatic door-closing devices are permitted if the fusible link rating does not exceed 135°F (57°C).
Related Code Sections
Section 704 Fire and Smoke Protection Features, Joints and Voids
Where required when the building was originally constructed, materials and systems used to protect joints and voids in the following locations shall ...
707.5 Fire and Smoke Protection Features, Continuity
ceiling. Joints and voids at intersections shall comply with Sections 707.8 and 707.9 Exceptions: Shaft enclosures shall be permitted ...
California Building Code 2016 (Vol 1 & 2) > 7 Fire and Smoke Protection Features > 707 Fire Barriers > 707.5 Continuity
707.5 Fire and Smoke Protection Features, Continuity
a suspended ceiling. Joints and voids at intersections shall comply with Sections 707.8 and 707.9 Exceptions: Shaft enclosures shall be permitted ...
California Building Code 2019 (Vol 1 & 2) > 7 Fire and Smoke Protection Features > 707 Fire Barriers > 707.5 Continuity
R606.3.2 Wall Construction, Masonry Unit Placement
joint. Deep furrowing of bed joints that produces voids shall not be permitted. Any units disturbed to the extent that initial bond is broken after ...
California Residential Code 2016 > 6 Wall Construction > R606 General Masonry Construction > R606.3 Construction Requirements > R606.3.2 Masonry Unit Placement
R606.3.2 Wall Construction, Masonry Unit Placement
joint. Deep furrowing of bed joints that produces voids shall not be permitted. Any units disturbed to the extent that initial bond is broken after ...
California Residential Code 2019 > 6 Wall Construction > R606 General Masonry Construction > R606.3 Construction Requirements > R606.3.2 Masonry Unit Placement