1616.5.1.1 Item 4. Assembly Areas
JUMP TO FULL CODE CHAPTER
The following minimum loads for stage accessories apply:
- Gridirons and fly galleries: 75 pounds per square foot uniform live load.
- Loft block wells: 250 pounds per lineal foot vertical load and lateral load.
- Head block wells and sheave beams: 250 pounds per lineal foot vertical load and lateral load. Head block wells and sheave beams shall be designed for all tributary loft block well loads. Sheave blocks shall be designed with a safety factor of five.
- Scenery beams where there is no gridiron: 300 pounds per lineal foot vertical load and lateral load.
- Ceiling framing over stages shall be designed for a uniform live load of 20 pounds per square foot. For members supporting a tributary area of 200 square feet or more, this additional load may be reduced to 15 pounds per square foot (0.72 kN/m2).
Related Code Sections
1616.5.1.1 Structural Design, Item 4. Assembly Areas
be designed for a uniform live load of 20 pounds per square foot. For members supporting a tributary area of 200 square feet or more, this additional ...
Los Angeles Building Code > 16 Structural Design > 1616 Additional Requirements for Community Colleges [DSA-SS/CC] > 1616.5 Live Loads > 1616.5.1 Modifications to Table 1607.1 > 1616.5.1.1 Item 4. Assembly Areas
714.4 Fire and Smoke Protection Features, Horizontal Assemblies
the aggregate area of the openings through the assembly does not exceed 144 square inches (92 900 mm 2 ) in any 100 square feet (9.3 m 2 ) of floor area ...
Los Angeles Building Code > 7 Fire and Smoke Protection Features > 714 Penetrations > 714.4 Horizontal Assemblies
714.5 Fire and Smoke Protection Features, Horizontal Assemblies
Penetrating items with a maximum 6-inch (152 mm) nominal diameter shall not be limited to the penetration of a single fire-resistance-rated floor assembly ...
Los Angeles Building Code > 7 Fire and Smoke Protection Features > 714 Penetrations > 714.5 Horizontal Assemblies
305A.4 Provisions for All Compliance Methods, Change of Occupancy
of occupancy in conjunction with alterations where the work area is 50 percent or less of the aggregate area of the building ...
Los Angeles Existing Building Code > 3A Provisions for All Compliance Methods > 305A Accessibility for Existing Buildings > 305A.4 Change of Occupancy
11B-221 Accessibility to Public Buildings, Public Accommodations, Commercial Buildings and Public Housing, Assembly Areas
Assembly areas shall provide wheelchair spaces, companion seats, designated aisle seats and semi-ambulant seats complying with Sections 11B -221 ...
Los Angeles Building Code > 11B Accessibility to Public Buildings, Public Accommodations, Commercial Buildings and Public Housing > 11B-221 Assembly Areas