An engineer shall scope and supervise the geotechnical investigation. The geotechnical investigation shall be sufficient for evaluating soil and rock conditions including, but not limited to, material classification, stratigraphy, groundwater, slope stability, soil and rock strength, adequacy of load-bearing soils and rock, the effect of moisture variation on soil-bearing capacity, compressibility, liquefaction and expansiveness. The investigation shall comply with Sections 1803.4.1 through 1803.4.4.
1803.4.1 Scope of Investigation
The scope of the geotechnical investigation, including the number, types and depths of borings, the number of test pits or the number of alternative test methods; the equipment used to drill and sample; the in-situ testing; and the laboratory testing program shall be determined by the engineer responsible for the investigation, subject to the requirements of this chapter.
  1. Borings shall be uniformly distributed under the structure or distributed in accordance with load patterns imposed by the structure.
  2. At a minimum, investigations for structures shall include:
    1. One exploratory boring for built-over areas up to and including 750 square feet (69.7 m2).
    2. Two exploratory borings for built-over areas greater than 750 square feet (69.7 m2) but less than 5,000 square feet (464.5 m2), and at least one additional boring for each additional 2,500 square feet (232.3 m2), or part thereof, of built-over areas up to 20,000 square feet (1858.1 m2).
    3. At least one boring for each additional 5,000 square feet (464.5 m2), or part thereof, of built-over areas in excess of 20,000 square feet (1858.1 m2).
  3. At a minimum, investigations for retaining walls greater than 10 feet (3048 mm) in height shall include one exploratory boring for every 50 linear feet (15 240 mm) of wall.
  4. Borings shall be taken into bedrock, or to an adequate depth below the top of the load-bearing strata to demonstrate that the foundation loads have been sufficiently dissipated and to evaluate global stability of retaining walls.
  5. For structures having an average area load (dead plus live) of 1,000 pounds per square foot (47.9 kN/m2) or more, at least one boring for every 10,000 square feet (929 m2) of footprint area shall penetrate at least 100 feet (30 480 mm) below the curb grade or 5 feet (1524 mm) into bedrock of Class 1c or better, whichever is less.
  6. At least one-half of the borings satisfying this requirement shall be located within the limits of the built-up area and the remainder shall be within 25 feet (7620 mm) of the built-up area limits.
  7. For structures to be supported on deep foundations, the required number of borings shall be not less than two borings, and based on a minimum of one boring per 2,000 square feet (184.8 m2) for the first 20,000 square feet (1858.1 m2) and one boring per every additional 4,000 square feet (371.6 m2) thereafter.
  8. All boring, sampling, and in-situ testing operations shall be subject to special inspection in accordance with Table 1705.6.
Exception: Test pits may be substituted for borings for one and two-story structures. The registered design professional shall submit a test pit observation report to the commissioner.
1803.4.2 Existing Data
Suitable borings, test pits, probings, and the logs and records that were obtained as part of earlier exploration programs by an engineer other than the engineer performing the geotechnical investigation and that meet the requirements of this section may only be used as partial fulfillment of the requirements of Section 1803.4.1. Additional boring(s) shall be made to fulfill the requirements of Section 1803.4.1, with a minimum of one additional boring required.
1803.4.3 Groundwater Table
The geotechnical investigation shall determine the existing groundwater table.
1803.4.4 Compressible Soils
In areas containing compressible soils, the geotechnical investigation shall determine the extent of these soils in the plan area of the structure and shall be subject to the requirements of Section 1803.3.

Related Code Sections

1802.4 Soils and Foundations, Investigation
An engineer shall scope and supervise the geotechnical investigation. The geotechnical investigation shall be sufficient for evaluating soil and rock ...
1803.4 Soils and Foundations, Investigation
An engineer shall scope and supervise the geotechnical investigation. The geotechnical investigation shall be sufficient for evaluating soil and rock ...
§28-502.9 Miscellaneous Provisions, Investigations
The department may investigate any matter within the jurisdiction conferred by this chapter and shall have full power to compel the attendance ...
§28-502.9 Miscellaneous Provisions, Investigations
The department may investigate any matter within the jurisdiction conferred by this chapter and shall have full power to compel the attendance ...