305.4 Interval of Support
JUMP TO FULL CODE CHAPTER
Piping shall be supported at distances not exceeding the spacing specified in Table 305.4, or in accordance with MSS SP-69.
TABLE 305.4
PIPING SUPPORT SPACINGa
PIPING MATERIAL | MAXIMUM HORIZONTAL SPACING (feet) | MAXIMUM VERTICAL SPACING (feet) |
ABS pipe | 4 | 10c |
Aluminum pipe and tubing | 10 | 15 |
Brass pipe | 10 | 10 |
Brass tubing, 11/4-inch diameter and smaller | 6 | 10 |
Brass tubing, 11/2-inch diameter and larger | 10 | 10 |
Cast-iron pipeb | 5 | 15 |
Copper or copper-alloy pipe | 12 | 10 |
Copper or copper-alloy tubing, 11/4-inch diameter and smaller | 6 | 10 |
Copper or copper-alloy tubing, 11/2-inch diameter and larger | 10 | 10 |
CPVC pipe or tubing, 1 inch and smaller | 3 | 10c |
CPVC pipe or tubing, 11/4-inch and larger | 4 | 10c |
Lead pipe | Continuous | 4 |
PB pipe or tubing | 22/3 (32 inches) | 4 |
PEX tubing | 22/3 (32 inches) | 10c |
Polypropylene (PP) pipe or tubing, 1 inch or smaller | 22/3 (32 inches) | 10c |
Polypropylene (PP) pipe or tubing, 11/4 inches or larger | 4 | 10c |
PVC pipe | 4 | 10c |
Steel tubing | 8 | 10 |
Steel pipe | 12 | 15 |
For SI: 1 inch = 25.4 mm, 1 foot = 304.8 mm.
- See Section 301.18.
- The maximum horizontal spacing of cast-iron pipe hangers shall be increased to 10 feet where 10-foot lengths of pipe are installed.
- Mid-story guide.
Related Code Sections
305.4 General Regulations, Interval of Support
Piping shall be supported at distances not exceeding the spacing specified in Table 305.4, or in accordance with ANSI/MSS SP-58. TABLE 305.4 ...
2017 FBC - Mechanical, 6th edition > 3 General Regulations > 305 Piping Support > 305.4 Interval of Support
305.4 General Regulations, Interval of Support
Piping shall be supported at distances not exceeding the spacing specified in Table 305.4, or in accordance with MSS SP-69. TABLE 305.4 PIPING ...
2014 FBC - Mechanical, 5th edition > 3 General Regulations > 305 Piping Support > 305.4 Interval of Support
305.4 General Regulations, Interval of Support
Piping shall be supported at distances not exceeding the spacing specified in Table 305.4, or in accordance with ANSI/MSS SP-58. TABLE 305.4 ...
2020 FBC - Mechanical, 7th edition > 3 General Regulations > 305 Piping Support > 305.4 Interval of Support
308.5 General Regulations, Interval of Support
Pipe shall be supported in accordance with Table 308.5. Exception: The interval of support for piping systems designed to provide for expansion ...
2014 FBC - Plumbing, 5th edition > 3 General Regulations > 308 Piping Support > 308.5 Interval of Support
308.5 General Regulations, Interval of Support
Pipe shall be supported in accordance with Table 308.5. Exception: The interval of support for piping systems designed to provide for expansion ...
2017 FBC - Plumbing, 6th edition > 3 General Regulations > 308 Piping Support > 308.5 Interval of Support