E3611.4 Interior Metal Water Piping
JUMP TO FULL CODE CHAPTER
Where grounding electrode conductors and bonding jumpers are connected to interior metal water piping as a means to extend the grounding electrode conductor connection to an electrode(s), such piping shall be located not more than 5 feet (1524 mm) from the point of entry into the building.
Where interior metal water piping is used as a conductor to interconnect electrodes that are part of the grounding electrode system, such piping shall be located not more than 5 feet (1524 mm) from the point of entry into the building. [250.68(C)(1)]
Related Code Sections
E3608.1.1.1 Services, Interior Metal Water Piping
Interior metal water piping located more than 5 feet (1524 mm) from the entrance to the building shall not be used as a conductor to interconnect ...
2017 FBC - Residential, 6th edition > 36 Services > E3608 Grounding Electrode System > E3608.1 Grounding Electrode System > E3608.1.1 Metal Underground Water Pipe > E3608.1.1.1 Interior Metal Water Piping
E3611.4 Services, Interior Metal Water Piping
Where grounding electrode conductors and bonding jumpers are connected to interior metal water piping as a means to extend the grounding electrode ...
2017 FBC - Residential, 6th edition > 36 Services > E3611 Grounding Electrode Conductor Connection to the Grounding Electrodes > E3611.4 Interior Metal Water Piping
E3611.4 Services, Interior Metal Water Piping
Where grounding electrode conductors and bonding jumpers are connected to interior metal water piping as a means to extend the grounding electrode ...
2014 FBC - Residential, 5th edition > 36 Services > E3611 Grounding Electrode Conductor Connection to the Grounding Electrodes > E3611.4 Interior Metal Water Piping
E3608.1.1 Services, Metal Underground Water Pipe
). Interior metal water piping located more than 5 feet (1524 mm) from the entrance to the building shall not be used as part of the grounding electrode ...
2014 FBC - Residential, 5th edition > 36 Services > E3608 Grounding Electrode System > E3608.1 Grounding Electrode System > E3608.1.1 Metal Underground Water Pipe
E3608.1 Services, Grounding Electrode System
) A metal underground water pipe that is in direct contact with the earth for 10 feet (3048 mm) or more, including any well casing ...
2017 FBC - Residential, 6th edition > 36 Services > E3608 Grounding Electrode System > E3608.1 Grounding Electrode System