Article 5 Interior Fire Alarm and Signal System
JUMP TO FULL CODE CHAPTER
- A closed circuit electrically supervised fire alarm signal system shall be installed in the following types of buildings:
- Hotels, motels, lodging houses, dormitories, and single room occupancies having more than fifteen sleeping rooms or accommodating more than fifteen lodgers above the first or ground story.
- Buildings classified in occupancy group H-1 or H-2. Systems installed in buildings where persons are restrained under the jurisdiction of an agency of the city or the state of New York may be modified to comply with the regulations of such agency, when such modification is approved by the commissioner.
- Day care agencies having a board of health permit for the accommodation of more than thirty children. If such day care agency is located at the grade level of the building, the fire alarm system is required only in the premises of the day care agency. If the day care agency is located at other than grade level of the building, an approved fire alarm system shall be provided throughout the building.
- Health clubs and turkish or other special treatment bath houses where there are sleeping accommodations for more than fifteen persons on the premises.
- Department stores or retail sales establishments having one or more floors above the street floor to which the public is admitted or with a total floor area of twenty thousand or more gross square feet.
- All public schools; also all private schools and university teaching buildings more than one story in height. If a school premise is located at other than a grade level of a building, an approved fire alarm system shall be provided throughout the building.
- Single and multi-tenant factory buildings more than two stories in height in which more than twenty-five persons are employed above the ground floor, as provided by section two hundred seventy-nine of the labor law. In buildings where more than ten per cent of the building occupancy is engaged in manufacturing, the building shall have an approved fire alarm system throughout.
- Buildings housing a motion picture studio.
- Buildings classified in occupancy group E, seventy-five feet or more in height and buildings classified in such occupancy group occupied or arranged to be occupied by an occupant load of more than one hundred persons above or below the street level or more than a total of five hundred persons in the entire building.
-
- Stages, dressing rooms and property rooms used in conjunction with all places of assembly used as cabarets.
- Places of assembly used as a cabaret.
- Areas containing gas distribution piping operating at levels above fifteen psig shall have a combustible gas detection-alarm system, and a suitable fire protection system as approved by the commissioner with the concurrence of the fire commissioner.
(a) Equipment and systems shall be made of approved materials, and shall be free from defective workmanship. The requirements of reference standard RS17-5 shall apply except as specifically qualified herein.
(b) Before any fire alarm system is installed or extended, approval shall be obtained from the commissioner.
(c) All devices and equipment that have been approved shall have securely fastened thereon a manufacturer's label indicating compliance with the requirements of section 27-135 of article eight of subchapter one of this chapter.
(b) Before any fire alarm system is installed or extended, approval shall be obtained from the commissioner.
(c) All devices and equipment that have been approved shall have securely fastened thereon a manufacturer's label indicating compliance with the requirements of section 27-135 of article eight of subchapter one of this chapter.
Except as provided in subdivisions (g) and (j) of section 27-972 of this article, fire alarm systems heretofore installed in buildings in accordance with rules then in force shall be accepted for use as long as they are maintained in good working order.
Fire alarms shall be classified as follows and shall meet the following general requirements:
(a) Uncoded closed circuit fire alarm system. Consisting of manually operated sending stations and audible signaling devices, so arranged that the operation of any station will automatically sound continuously the signaling devices throughout all portions of the building.
(b) Master coded closed circuit fire alarm systems. Consisting of manually operated pull-lever type sending stations and audible signaling devices, so arranged that the operation of any station will automatically sound the signaling devices giving a common code of signals throughout all portions of the building. The code shall consist of four rounds of a series of single strokes of the signaling devices, each round consisting of "3-3-3-3".
(c) Individually coded closed circuit general fire alarm systems. Consisting of manually operated pull-lever type sending stations and audible signaling devices, so arranged that the operation of any station will automatically sound the signaling devices, throughout all portions of the building, for a minimum of four rounds of a distinctive code of signals particular to the station at which the signal has been initiated. The code numbers that are used shall be subject to the approval of the fire commissioner.
(d) Individually coded closed circuit presignal fire alarm systems. Consisting of manually operated pull-lever type sending stations and signal devices so arranged that the operation of any station will cause the sound of only the signal devices located in the engine room and basement and other places in the building where the members of a fire brigade work or assemble. The signaling device shall give four rounds of the particular code signal of the station at which the signal has been initiated. Approved equipment shall be provided at each station so that the operation of any station performed with the aid of a key or plug will sound all of the signal devices located in the building with four rounds of the particular coded signal of the station initiated. The code numbers used shall be subject to the approval of the fire commissioner. The presignal key or plug shall be so designed that it can be readily identified. Presignal type systems will not generally be approved; however, approval may be obtained from the fire commissioner where special type occupancies may warrant such a system.
(e) Combination unit or zone, and general alarm coded closed circuit fire alarm systems. Consisting of manually operated pull-lever type sending stations and signal devices so arranged that the operation of any station will cause all of the signaling devices in that unit or zone to sound four rounds of the particular coded signal of the station initiated, and simultaneously will cause all of the signaling devices on the general alarm circuit to sound four rounds of the coded signal designating the unit or zone in which the station is located. An approved register and time stamp may be used in connection with this system when approved by the fire commissioner. The register, if of the closed circuit type, shall be operated from a separate closed circuit control board or panel isolated by a barrier from the main control panel in the main fire alarm control cabinet. An approved closed circuit unit annunciator with trouble alarm circuit shall be installed as part of this system when required by the fire commissioner.
(f) Special systems. Consisting of the above systems as required, supplemented by special circuits for the operation of other fire alarm or detection devices in the systems, or electric control systems for stopping machinery, closing doors or ventilators, or shutting down fans as may be required by the commissioner or the code, or to call the central station of a private operating company of the fire department. Automatic fire detecting systems may be connected to operate an interior fire alarm system when connected thereto by an approved coded transmitter. In no case shall the transmitter be considered to replace the standard approved interior fire alarm station, except where a transmitter has been approved for both purposes. The special control circuits and devices shall be separate and distinct from the fire alarm system but shall be brought into action whenever the fire alarm system is set in operation.
(g) Class E system.--Consisting of a class E fire alarm signal system as described in subdivision (f) of section 27-972 of article five of this subchapter and reference standard RS17-3A. Such systems shall be exempt from the provisions of section 27-973 of article five of this subchapter, except that compliance with paragraph two of subdivision (a) and subdivision (e) of such section shall be required.
(h) Modified class E system.--Consisting of a modified class E fire alarm signal system as described in subdivision (g) of section 27-972 of article five of this subchapter and reference standard RS17-3B. Such systems shall be exempt from the provisions of section 27-973 of article five of this subchapter, except that compliance with paragraph two of subdivision (a) and subdivision (e) of such section shall be required.
(i) Class C system.--Consisting of a class C fire alarm signal system as described in subdivision (k) of section 27-972 and reference standard RS 17-3A. Such systems shall be exempt from the provisions of section 27-973 of article five of this subchapter, except that compliance with paragraph two of subdivision (a) and subdivision (e) of such section shall be required.
(j) Class J system.--Consisting of a class J fire alarm signal system as described in subdivision (l) of section 27-972 of article five of this subchapter and reference standard RS 17-3A. Such systems shall be exempt from the provisions of section 27-973 of article five of this subchapter, except that compliance with paragraph two of subdivision (a) and subdivision (e) of such section shall be required.
(k) Modified class J system.--Consisting of a modified class J fire alarm signal system as described in subdivision (m) of section 27-972 of article five of this subchapter and reference standard RS 17-3B. Such systems shall be exempt from the provisions of section 27-973 of article five of this subchapter, except that compliance with paragraph two of subdivision (a) and subdivision (e) of such section shall be required.
(l) Modified class J-1 system.--Consisting of a modified class J-1 fire alarm signal system as described in paragraph two of subdivision (j) of section 27-972 of article five of this subchapter.
(a) Uncoded closed circuit fire alarm system. Consisting of manually operated sending stations and audible signaling devices, so arranged that the operation of any station will automatically sound continuously the signaling devices throughout all portions of the building.
(b) Master coded closed circuit fire alarm systems. Consisting of manually operated pull-lever type sending stations and audible signaling devices, so arranged that the operation of any station will automatically sound the signaling devices giving a common code of signals throughout all portions of the building. The code shall consist of four rounds of a series of single strokes of the signaling devices, each round consisting of "3-3-3-3".
(c) Individually coded closed circuit general fire alarm systems. Consisting of manually operated pull-lever type sending stations and audible signaling devices, so arranged that the operation of any station will automatically sound the signaling devices, throughout all portions of the building, for a minimum of four rounds of a distinctive code of signals particular to the station at which the signal has been initiated. The code numbers that are used shall be subject to the approval of the fire commissioner.
(d) Individually coded closed circuit presignal fire alarm systems. Consisting of manually operated pull-lever type sending stations and signal devices so arranged that the operation of any station will cause the sound of only the signal devices located in the engine room and basement and other places in the building where the members of a fire brigade work or assemble. The signaling device shall give four rounds of the particular code signal of the station at which the signal has been initiated. Approved equipment shall be provided at each station so that the operation of any station performed with the aid of a key or plug will sound all of the signal devices located in the building with four rounds of the particular coded signal of the station initiated. The code numbers used shall be subject to the approval of the fire commissioner. The presignal key or plug shall be so designed that it can be readily identified. Presignal type systems will not generally be approved; however, approval may be obtained from the fire commissioner where special type occupancies may warrant such a system.
(e) Combination unit or zone, and general alarm coded closed circuit fire alarm systems. Consisting of manually operated pull-lever type sending stations and signal devices so arranged that the operation of any station will cause all of the signaling devices in that unit or zone to sound four rounds of the particular coded signal of the station initiated, and simultaneously will cause all of the signaling devices on the general alarm circuit to sound four rounds of the coded signal designating the unit or zone in which the station is located. An approved register and time stamp may be used in connection with this system when approved by the fire commissioner. The register, if of the closed circuit type, shall be operated from a separate closed circuit control board or panel isolated by a barrier from the main control panel in the main fire alarm control cabinet. An approved closed circuit unit annunciator with trouble alarm circuit shall be installed as part of this system when required by the fire commissioner.
(f) Special systems. Consisting of the above systems as required, supplemented by special circuits for the operation of other fire alarm or detection devices in the systems, or electric control systems for stopping machinery, closing doors or ventilators, or shutting down fans as may be required by the commissioner or the code, or to call the central station of a private operating company of the fire department. Automatic fire detecting systems may be connected to operate an interior fire alarm system when connected thereto by an approved coded transmitter. In no case shall the transmitter be considered to replace the standard approved interior fire alarm station, except where a transmitter has been approved for both purposes. The special control circuits and devices shall be separate and distinct from the fire alarm system but shall be brought into action whenever the fire alarm system is set in operation.
(g) Class E system.--Consisting of a class E fire alarm signal system as described in subdivision (f) of section 27-972 of article five of this subchapter and reference standard RS17-3A. Such systems shall be exempt from the provisions of section 27-973 of article five of this subchapter, except that compliance with paragraph two of subdivision (a) and subdivision (e) of such section shall be required.
(h) Modified class E system.--Consisting of a modified class E fire alarm signal system as described in subdivision (g) of section 27-972 of article five of this subchapter and reference standard RS17-3B. Such systems shall be exempt from the provisions of section 27-973 of article five of this subchapter, except that compliance with paragraph two of subdivision (a) and subdivision (e) of such section shall be required.
(i) Class C system.--Consisting of a class C fire alarm signal system as described in subdivision (k) of section 27-972 and reference standard RS 17-3A. Such systems shall be exempt from the provisions of section 27-973 of article five of this subchapter, except that compliance with paragraph two of subdivision (a) and subdivision (e) of such section shall be required.
(j) Class J system.--Consisting of a class J fire alarm signal system as described in subdivision (l) of section 27-972 of article five of this subchapter and reference standard RS 17-3A. Such systems shall be exempt from the provisions of section 27-973 of article five of this subchapter, except that compliance with paragraph two of subdivision (a) and subdivision (e) of such section shall be required.
(k) Modified class J system.--Consisting of a modified class J fire alarm signal system as described in subdivision (m) of section 27-972 of article five of this subchapter and reference standard RS 17-3B. Such systems shall be exempt from the provisions of section 27-973 of article five of this subchapter, except that compliance with paragraph two of subdivision (a) and subdivision (e) of such section shall be required.
(l) Modified class J-1 system.--Consisting of a modified class J-1 fire alarm signal system as described in paragraph two of subdivision (j) of section 27-972 of article five of this subchapter.
Related Code Sections
Article 5 Fire Alarm, Detection and Extinguishing Equipment, Interior Fire Alarm and Signal System
signal system consisting of an interior fire alarm and voice communicating system so arranged that the operation of any station will identify its location ...
NYC 1968 Code (Vol I) > 17 Fire Alarm, Detection and Extinguishing Equipment > 5 Interior Fire Alarm and Signal System
§27-975 Fire Alarm, Detection and Extinguishing Equipment, Communication System and Fire Command Station
to control the sounding devices on any floor or throughout the building. (5) means to manually transmit a fire alarm signal to the fire department via ...
NYC 1968 Code (Vol I) > 17 Fire Alarm, Detection and Extinguishing Equipment > 5 Interior Fire Alarm and Signal System > §27-975 Communication System and Fire Command Station
§27-968 Fire Alarm, Detection and Extinguishing Equipment, Where Required
A closed circuit electrically supervised fire alarm signal system shall be installed in the following types of buildings:
Hotels, motels ...
NYC 1968 Code (Vol I) > 17 Fire Alarm, Detection and Extinguishing Equipment > 5 Interior Fire Alarm and Signal System > §27-968 Where Required
§27-969 Fire Alarm, Detection and Extinguishing Equipment, Approvals
RS17-5 shall apply except as specifically qualified herein. (b) Before any fire alarm system is installed or extended, approval shall be obtained from ...
NYC 1968 Code (Vol I) > 17 Fire Alarm, Detection and Extinguishing Equipment > 5 Interior Fire Alarm and Signal System > §27-969 Approvals
§27-970 Fire Alarm, Detection and Extinguishing Equipment, Existing Installations
Except as provided in subdivisions (g) and (j) of section 27-972 of this article, fire alarm systems heretofore installed in buildings in accordance ...
NYC 1968 Code (Vol I) > 17 Fire Alarm, Detection and Extinguishing Equipment > 5 Interior Fire Alarm and Signal System > §27-970 Existing Installations