7.1.4.1* Interior Wall and Ceiling Finish in Exit Enclosures
Interior wall and ceiling finish shall be in accordance with Section 10.2. In exit enclosures, interior wall and ceiling finish materials complying with Section 10.2 shall be Class A or Class B.
7.1.4.2* Interior Floor Finish in Exit Enclosures
New interior floor finish in exit enclosures, including stair treads and risers, shall be not less than Class II in accordance with Section 10.2.