This model is based on an institutionalized medical program similar in arrangement to that found in some hospitals. If this model is utilized for the design of the resident unit, it shall consist of the resident rooms, nurse station(s), and resident support areas and services as described in Section 450.3.4.1. Dining, activity, and social areas may be centralized and located away from the resident unit.
450.3.2.1.1
Each resident unit shall be limited to a maximum of 60 beds.
450.3.2.1.2
Travel distance from the entrance to a nurses' station, and from a clean utility and a soiled utility room(s) or function(s) to the middle of the entrance door of the farthest resident room served shall be a maximum of 150 feet (45.72 m).