60.5.1.19 Installation of Tanks
JUMP TO FULL CODE CHAPTER
Underground tanks used for the storage of liquid hazardous materials shall be provided with secondary containment. [400:6.1.19.1.1]
In lieu of providing secondary containment for an underground tank, an aboveground tank in an underground vault complying with NFPA 30 shall be permitted. [400:6.1.19.1.2]
Aboveground stationary tanks installed outdoors and used for the storage of hazardous materials shall be located and protected in accordance with the requirements for outdoor storage of the particular material involved and in accordance with the requirements of Chapters 11 through 21 of NFPA 400. [400:6.1.19.2]
Aboveground tanks that are installed in vaults complying with NFPA 30 shall not be required to comply with location and protection requirements for outdoor storage. [400:6.1.19.2.1]
Aboveground tanks that are installed inside buildings and used for the storage of hazardous materials shall be located and protected in accordance with the requirements for indoor storage of the particular material involved. [400:6.1.19.2.2]
Aboveground stationary tanks shall be marked as required by 60.5.1.8.2.1. [400:6.1.19.2.3]
Related Code Sections
60.5.1.19 Hazardous Materials, Installation of Tanks
Installation of tanks shall be in accordance with 60.5.1.19.1 through 60.5.1.19.2. [400:6.1.19 ...
Fire Code 2018 of Maine > 60 Hazardous Materials > 60.5 Fundamental Requirements > 60.5.1 General Requirements > 60.5.1.19 Installation of Tanks
60.5.1.19.1.1 Hazardous Materials,
Underground tanks used for the storage of liquid hazardous materials shall be provided with secondary containment. [400:6.1.19.1.1] ...
Fire Code 2018 of Maine > 60 Hazardous Materials > 60.5 Fundamental Requirements > 60.5.1 General Requirements > 60.5.1.19 Installation of Tanks > 60.5.1.19.1 Underground Tanks > 60.5.1.19.1.1
60.5.1.19.1.2 Hazardous Materials,
In lieu of providing secondary containment for an underground tank, an aboveground tank in an underground vault complying with NFPA 30 shall ...
Fire Code 2018 of Maine > 60 Hazardous Materials > 60.5 Fundamental Requirements > 60.5.1 General Requirements > 60.5.1.19 Installation of Tanks > 60.5.1.19.1 Underground Tanks > 60.5.1.19.1.2
66.25.5* Flammable and Combustible Liquids, Construction and Installation of Storage Tank Vaults
] The top of an abovegrade vault that contains a tank storing Class I liquid or Class II liquid ...
Fire Code 2018 of Maine > 66 Flammable and Combustible Liquids > 66.25 Storage Tank Vaults > 66.25.5* Construction and Installation of Storage Tank Vaults
42.3.3.3.3* Refueling, Construction and Installation of Storage Tank Vaults
] Storage tank vaults shall be installed in accordance with the requirements of 42.3.3.3.3.2.1 and 42.3.3.3.3.2.2. [30:25.5.2 ...
Fire Code 2018 of Maine > 42 Refueling > 42.3 Storage of Liquids > 42.3.3 Storage of Liquids > 42.3.3.3 Vaults for Aboveground Tanks > 42.3.3.3.3* Construction and Installation of Storage Tank Vaults