1308.1 Installation of Piping System
JUMP TO FULL CODE CHAPTER
Where required by the
Authority Having Jurisdiction, a piping sketch or plan shall be
prepared before proceeding with the installation. This plan
shall show the proposed location of piping, the size of
different branches, the various load demands, and the location
of the point of delivery. [NFPA 54:5.1.1]
Where additional appliances are being connected to a gas piping system, the existing piping shall be checked to determine whether it has adequate capacity. Where inadequate, the existing system shall be enlarged as required, or separate gas piping of approved capacity shall be provided. [NFPA 54:5.1.2]
Related Code Sections
1208.1 Fuel Gas Piping, Installation of Piping System
Where required by the Authority Having Jurisdiction, a piping sketch or plan
shall be prepared before proceeding with the installation. The plan ...
Los Angeles Plumbing Code > 12 Fuel Gas Piping > 1208.0 Gas Piping System Design, Materials, and Components > 1208.1 Installation of Piping System
1308.1 Fuel Gas Piping, Installation of Piping System
Where required by the
Authority Having Jurisdiction, a piping sketch or plan shall be
prepared before proceeding with the installation. This plan ...
Los Angeles Mechanical Code > 13 Fuel Gas Piping > 1308.0 Gas Piping System Design, Materials, and Components > 1308.1 Installation of Piping System
1308.1 Fuel Gas Piping, Installation of Piping System
Where required
by the Authority Having Jurisdiction, a piping sketch or plan
shall be prepared before proceeding with the installation. The
plan ...
Los Angeles Mechanical Code > 13 Fuel Gas Piping > 1308.0 Gas Piping System Design, Materials, and Components > 1308.1 Installation of Piping System